Assessment Year | 1988 |
---|---|
Principal Product | GRAN. SUGAR, CATTLE FEED |
NAICS |
n/a
|
SIC | 2063: Beet Sugar |
Sales Range | $10 M to 50M |
# of Employees | 200 |
Plant Area |
n/a
|
Annual Production | 0
units
|
Production Hrs. Annual | 3,600
hrs
|
Location (State) | Nebraska |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $270,780 | 7,305,100 |
kWh
|
$0.037 |
Natural Gas | $39,110 | 8,657 |
MMBtu
|
$4.52 |
Coal | $1,274,834 | 1,098,489 |
MMBtu
|
$1.16 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $271,238 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $267,848 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Coal Savings |
---|---|---|---|---|---|---|---|
01 | 2.1233: Analyze flue gas for proper air/fuel ratio | $151,329 | $7,000 | - | - |
$151,329
-
MMBtu
|
|
02 | 2.2136: Install / repair insulation on steam lines | $753 | $18,000 | - | - |
$753
-
MMBtu
|
|
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,758 | - |
$2,540
68,581
kWh
|
- |
$218
-
MMBtu
|
|
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $5,814 | $7,000 |
$5,354
144,490
kWh
|
- |
$460
-
MMBtu
|
|
05 | 2.7261: Install timers and/or thermostats | $3,390 | $375 | - |
$3,390
-
MMBtu
|
- | |
06 | 2.2414: Use waste heat from hot flue gases to preheat | $107,194 | $100,000 | - | - |
$107,194
-
MMBtu
|
|
TOTAL RECOMMENDED | $271,238 | $132,375 |
$7,894
213,071
kWh
|
$3,390
-
MMBtu
|
$259,954
-
MMBtu
|
||
TOTAL IMPLEMENTED | $267,848 | $132,000 |
$7,894
213,071
kWh
|
- |
$259,954
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Coal Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs