| Assessment Year | 1987 |
|---|---|
| Principal Product | CAPACITORS,SHEET METAL BOXES |
| NAICS |
n/a
|
| SIC | 3675: Electronic Capacitors |
| Sales Range | $1 M to 5M |
| # of Employees | 100 |
| Plant Area |
n/a
|
| Annual Production | 5,000,000
pieces
|
| Production Hrs. Annual | 2,210
hrs
|
| Location (State) | Nebraska |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $61,235 | 1,110,492 |
kWh
|
$0.055 |
| Natural Gas | $21,018 | 4,468 |
MMBtu
|
$4.70 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $8,946 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $8,873 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $381 | $200 |
$381
7,034
kWh
|
- | |
| 02 | 2.4221: Install compressor air intakes in coolest locations | $73 | $100 |
$73
1,465
kWh
|
- | |
| 03 | 2.2437: Recover waste heat from equipment | $528 | $350 | - |
$528
-
MMBtu
|
|
| 04 | 2.3191: Use demand controller or load shedder | $689 | $1,200 |
$689
-
kWh
|
- | |
| 05 | 2.7229: Air condition only space necessary | $556 | $100 |
$556
9,965
kWh
|
- | |
| 06 | 2.7243: Improve air circulation with destratification fans / other methods | $375 | $500 |
$(-42.0)
(-879)
kWh
|
$417
-
MMBtu
|
|
| 07 | 2.7221: Lower temperature during the winter season and vice-versa | $4,133 | $2,000 | - |
$4,133
-
MMBtu
|
|
| 08 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,147 | $1,350 | - |
$1,147
-
MMBtu
|
|
| 09 | 2.7492: Use proper thickness of insulation on building envelope | $65 | $90 | - |
$65
-
MMBtu
|
|
| 10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $999 | $1,000 |
$999
18,171
kWh
|
- | |
| TOTAL RECOMMENDED | $8,946 | $6,890 |
$2,656
35,756
kWh
|
$6,290
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $8,873 | $6,790 |
$2,583
34,291
kWh
|
$6,290
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs