| Assessment Year | 1985 |
|---|---|
| Principal Product | NEWSPAPERS |
| NAICS |
n/a
|
| SIC | 2711: Newspapers: Publishing, or Publishing and Printing |
| Sales Range | $5 M to 10M |
| # of Employees | 140 |
| Plant Area |
n/a
|
| Annual Production | 9,000,000
pieces
|
| Production Hrs. Annual | 4,056
hrs
|
| Location (State) | Colorado |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $63,013 | 827,374 |
kWh
|
$0.076 |
| Natural Gas | $13,285 | 2,433 |
MMBtu
|
$5.46 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $14,200 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $12,095 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,993 | $2,632 |
$5,993
78,839
kWh
|
- | |
| 02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $2,084 | $350 | - |
$2,084
-
MMBtu
|
|
| 03 | 2.2425: Use flue gases to heat process or service water | $689 | $450 | - |
$689
-
MMBtu
|
|
| 04 | 2.3191: Use demand controller or load shedder | $1,378 | $1,800 |
$1,378
-
kWh
|
- | |
| 05 | 2.7261: Install timers and/or thermostats | $2,105 | $420 |
$882
11,723
kWh
|
$1,223
-
MMBtu
|
|
| 06 | 2.7226: Use computer programs to optimize hvac performance | $1,951 | $4,000 |
$1,951
25,498
kWh
|
- | |
| TOTAL RECOMMENDED | $14,200 | $9,652 |
$10,204
116,060
kWh
|
$3,996
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $12,095 | $9,232 |
$9,322
104,337
kWh
|
$2,773
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs