| Assessment Year | 2025 |
|---|---|
| Principal Product | structural steel and industrial steel fabrication, art structures, machining, and roofing machines |
| NAICS | 332312: Fabricated Structural Metal Manufacturing |
| SIC | 3441: Fabricated Structural Metal |
| Sales Range | $10 M to 50M |
| # of Employees | 120 |
| Plant Area |
150,000
ft2
|
| Annual Production | 15,000
ton
|
| Production Hrs. Annual | 2,592
hrs
|
| Location (State) | Colorado |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $60,006 | 1,455,549 |
kWh
|
$0.041 |
| Electricity Demand | $115,605 | 5,723 |
kW-mo/yr
|
$20.20 |
| Electricity Fees | $21,750 | - |
|
- |
| Natural Gas | $59,566 | 7,798 |
MMBtu
|
$7.64 |
| TOTAL YEARLY COSTS | $256,927 | |||
| RECOMMENDED SAVINGS* | $149,458 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (haz) Savings | Personnel Changes Savings | By-product Production Savings |
|---|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.9114: Use solar heat to make electricty | $23,130 | $291,962 |
$16,062
389,856
kWh
|
$7,068
-
kW-mo/yr
|
- | - | - | - | |
| 02 | 2.4322: Use or replace with energy efficient substitutes | $59,719 | $280,000 |
$6,565
159,256
kWh
|
$12,726
-
kW-mo/yr
|
- | - | - | $40,428 | |
| 03 | 2.7232: Replace existing hvac unit with high efficiency model | $10,339 | $132,216 |
$4,936
119,814
kWh
|
$5,403
-
kW-mo/yr
|
- | - | - | - | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,347 | $7,094 |
$1,635
39,684
kWh
|
$3,712
-
kW-mo/yr
|
- | - | - | - | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,515 | $84 |
$1,381
33,507
kWh
|
$3,134
-
kW-mo/yr
|
- | - | - | - | |
| 06 | 2.2437: Recover waste heat from equipment | $1,789 | $300 |
$467
11,342
kWh
|
$1,322
-
kW-mo/yr
|
- | - | - | - | |
| 07 | 2.4221: Install compressor air intakes in coolest locations | $437 | $3,623 |
$437
10,606
kWh
|
- | - | - | - | - | |
| 08 | 2.7493: Use double or triple glazed windows to maintain higher relative humidity and to reduce heat losses | $192 | $1,678 | - | - |
$192
-
MMBtu
|
- | - | - | |
| 09 | 2.8226: Increase efficiency of trucks | $43,990 | $273,305 |
$(-2,236.0)
(-54,278)
kWh
|
- | - |
$41,906
-
gal
|
$4,320 | - | |
| TOTAL RECOMMENDED | $149,458 | $990,262 |
$29,247
709,787
kWh
|
$33,365
-
kW-mo/yr
|
$192
-
MMBtu
|
$41,906
-
gal
|
$4,320 | $40,428 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (haz) Savings | Personnel Changes Savings | By-product Production Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs