Assessment Year | 2023 |
---|---|
Principal Product | Dimensional Graphics |
NAICS | 313210: Broadwoven Fabric Mills |
SIC | 2261: Finishers of Broadwoven Fabrics of Cotton |
Sales Range | $5 M to 10M |
# of Employees | 40 |
Plant Area |
58,700
ft2
|
Annual Production | 120,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Colorado |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $31,157 | 687,840 |
kWh
|
$0.045 |
Electricity Demand | $62,014 | 3,145 |
kW-mo/yr
|
$19.72 |
Electricity Fees | $6,954 | - |
|
- |
Natural Gas | $25,171 | 2,975 |
MMBtu
|
$8.46 |
TOTAL YEARLY COSTS | $125,296 | |||
RECOMMENDED SAVINGS* | $40,193 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $30,313 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.2622: Replace existing chiller with high efficiency model | $4,638 | $57,344 |
$1,582
34,915
kWh
|
$3,056
-
kW-mo/yr
|
- | - | |
02 | 2.6218: Turn off equipment when not in use | $738 | - |
$738
16,304
kWh
|
- | - | - | |
03 | 2.2622: Replace existing chiller with high efficiency model | $1,890 | $15,750 |
$687
15,163
kWh
|
$1,203
-
kW-mo/yr
|
- | - | |
04 | 2.1224: Replace boiler | $20,045 | $41,481 |
$(-554.0)
(-12,230)
kWh
|
$(-464.0)
-
kW-mo/yr
|
$21,063
-
MMBtu
|
- | |
05 | 2.7493: Use double or triple glazed windows to maintain higher relative humidity and to reduce heat losses | $1,538 | $4,396 |
$104
2,307
kWh
|
- |
$1,434
-
MMBtu
|
- | |
06 | 4.444: Install system to collect scrap | $9,880 | $2,306 | - | - | - | $9,880 | |
07 | 2.1321: Replace fossil fuel equipment with electrical equipment | $1,464 | $3,500 |
$(-98.0)
(-2,156)
kWh
|
$(-291.0)
-
kW-mo/yr
|
$1,853
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $40,193 | $124,777 |
$2,459
54,303
kWh
|
$3,504
-
kW-mo/yr
|
$24,350
-
MMBtu
|
$9,880 | ||
TOTAL IMPLEMENTED | $30,313 | $122,471 |
$2,459
54,303
kWh
|
$3,504
-
kW-mo/yr
|
$24,350
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs