ITAC Assessment: CI0087
ITAC logo
ITAC Assessment: CI0087
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2026
Principal Product Lodging and Hospitality Services
NAICS 721110: Hotels (except Casino Hotels) and Motels
SIC 7011: Hotels and Motels
Sales Range $50
M
to 100
M
# of Employees 422
Plant Area 634,369
ft2
Annual Production 500,000
units
Production Hrs. Annual 8,760
hrs
Location (State) California

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $1,446,092 7,248,000
kWh
Electricity Demand $229,743 15,806
kW-mo/yr
Electricity Fees $229,520 -
Natural Gas $201,300 14,127
MMBtu
Other Gas $19,068 1
MMBtu
Waste Disposal Costs
Water Usage $169,442 11,724
Tgal
Water Disposal $145,379 11,724
Tgal
Other Liquid (non-haz) $30,600 1
gal
TOTAL YEARLY COSTS $2,471,144
RECOMMENDED SAVINGS* $405,398 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
01 2.9114: Use solar heat to make electricty $149,761 $359,788 $135,140
693,027
kWh
$14,621
-
kW-mo/yr
-
02 2.7262: Separate controls of air handlers from ac/ heating systems $144,960 $200,000 $144,960
724,800
kWh
- -
03 2.2622: Replace existing chiller with high efficiency model $56,064 $81,000 $56,064
280,320
kWh
- -
04 2.1224: Replace boiler $32,787 $140,000 - - $32,787
-
MMBtu
05 2.4239: Eliminate or reduce compressed air usage $8,428 $15,000 $7,842
39,210
kWh
$586
-
kW-mo/yr
-
06 2.7316: Centralize control of exhaust fans to ensure their shutdown, or establish program to ensure manual shutdown $4,897 $2,400 $3,921
19,605
kWh
$976
-
kW-mo/yr
-
07 2.4133: Use most efficient type of electric motors $3,917 $720 $3,645
18,227
kWh
$272
-
kW-mo/yr
-
08 2.7232: Replace existing hvac unit with high efficiency model $2,904 $20,720 $2,206
44,110
kWh
$698
-
kW-mo/yr
-
09 2.2136: Install / repair insulation on steam lines $1,680 $7,650 - - $1,680
-
MMBtu
TOTAL RECOMMENDED $405,398 $827,278 $353,778
1,819,299
kWh
$17,153
-
kW-mo/yr
$34,467
-
MMBtu
TOTAL IMPLEMENTED - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs