Assessment Year | 2025 |
---|---|
Principal Product | Meat Snacks |
NAICS | 311612: Meat Processed from Carcasses |
SIC | 2013: Sausages and Other Prepared Meat Products |
Sales Range | $10 M to 50M |
# of Employees | 40 |
Plant Area |
14,000
ft2
|
Annual Production | 2,000,000
lb
|
Production Hrs. Annual | 2,080
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $80,720 | 486,572 |
kWh
|
$0.17 | |
Electricity Demand | $24,525 | 1,497 |
kW-mo/yr
|
$16.38 | |
Electricity Fees | $13,869 | - |
|
- | |
Natural Gas | $54,188 | 5,177 |
MMBtu
|
$10.47 | |
Other Gas | $15,268 | 1 |
MMBtu
|
$15,268.00 | |
Waste Disposal Costs | |||||
Water Usage | $8,130 | 616 |
Tgal
|
$13.20 | |
Water Disposal | $4,498 | 616 |
Tgal
|
$7.30 | |
TOTAL YEARLY COSTS | $201,198 | ||||
RECOMMENDED SAVINGS* | $105,012 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings | Primary Product Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7447: Install vinyl strip / high speed / air curtain doors | $43,028 | $180,000 |
$21,968
132,416
kWh
|
- | - | $21,060 | - | |
02 | 2.4323: Use optimum size and capacity equipment | $15,529 | $100,000 | - | - |
$2,029
-
MMBtu
|
- | $13,500 | |
03 | 2.9114: Use solar heat to make electricty | $13,426 | $93,790 |
$11,362
68,486
kWh
|
$2,064
-
kW-mo/yr
|
- | - | - | |
04 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $10,940 | $13,970 |
$10,940
65,942
kWh
|
- | - | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $8,848 | $9,000 |
$5,638
33,982
kWh
|
$3,210
-
kW-mo/yr
|
- | - | - | |
06 | 2.2511: Insulate bare equipment | $5,585 | $8,530 | - | - |
$5,585
-
MMBtu
|
- | - | |
07 | 2.4226: Use / purchase optimum sized compressor | $5,415 | $5,000 |
$3,449
20,791
kWh
|
$1,966
-
kW-mo/yr
|
- | - | - | |
08 | 2.3132: Recharge batteries on during off-peak demand periods | $2,241 | $1,500 | - |
$2,241
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $105,012 | $411,790 |
$53,357
321,617
kWh
|
$9,481
-
kW-mo/yr
|
$7,614
-
MMBtu
|
$21,060 | $13,500 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings | Primary Product Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs