Assessment Year | 2025 |
---|---|
Principal Product | Supermarket Display Fixtures |
NAICS | 337215: Showcase, Partition, Shelving, and Locker Manufacturing |
SIC | 2541: Wood Office and Store Fixtures, Partitions, Shelving, and Lockers |
Sales Range | $10 M to 50M |
# of Employees | 65 |
Plant Area |
18,500
ft2
|
Annual Production | 18,000,000
pieces
|
Production Hrs. Annual | 6,120
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $71,835 | 317,446 |
kWh
|
$0.23 |
Electricity Demand | $40,077 | 3,216 |
kW-mo/yr
|
$12.46 |
Electricity Fees | $10,759 | - |
|
- |
Natural Gas | $131 | 9 |
MMBtu
|
$14.56 |
LPG | $9,180 | 428 |
MMBtu
|
$21.43 |
Other Gas | $206 | 1 |
MMBtu
|
$206.00 |
TOTAL YEARLY COSTS | $132,188 | |||
RECOMMENDED SAVINGS* | $132,418 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | LPG Savings | Administrative Changes Savings | Ancillary Material Cost Savings | Increase in Production Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.9114: Use solar heat to make electricty | $57,161 | $288,868 |
$52,210
230,710
kWh
|
$4,951
-
kW-mo/yr
|
- | - | - | - | |
02 | 2.2622: Replace existing chiller with high efficiency model | $34,278 | $75,000 |
$34,278
151,470
kWh
|
- | - | - | - | - | |
03 | 2.4322: Use or replace with energy efficient substitutes | $21,951 | $31,000 |
$21,951
97,002
kWh
|
- | - | - | - | - | |
04 | 2.8227: Adjust / maintain fork lift trucks for most efficient operation | $7,997 | $19,000 |
$(-763.0)
(-3,370)
kWh
|
$(-420.0)
-
kW-mo/yr
|
$9,180
-
MMBtu
|
- | - | - | |
05 | 2.7134: Use photocell controls | $5,246 | $7,920 |
$3,890
17,191
kWh
|
$885
-
kW-mo/yr
|
- | $213 | $258 | - | |
06 | 2.4226: Use / purchase optimum sized compressor | $2,911 | $6,699 |
$(-16,089.0)
(-71,096)
kWh
|
- | - | - | - | $19,000 | |
07 | 2.7493: Use double or triple glazed windows to maintain higher relative humidity and to reduce heat losses | $2,874 | $7,990 |
$2,874
12,698
kWh
|
- | - | - | - | - | |
TOTAL RECOMMENDED | $132,418 | $436,477 |
$98,351
434,605
kWh
|
$5,416
-
kW-mo/yr
|
$9,180
-
MMBtu
|
$213 | $258 | $19,000 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | LPG Savings | Administrative Changes Savings | Ancillary Material Cost Savings | Increase in Production Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs