| Assessment Year | 2023 |
|---|---|
| Principal Product | Academic Service |
| NAICS | 611110: Elementary and Secondary Schools |
| SIC | 8211: Elementary and Secondary Schools |
| Sales Range | less than $500 k |
| # of Employees | 122 |
| Plant Area |
216,563
ft2
|
| Annual Production | 1
units
|
| Production Hrs. Annual | 1,500
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $254,721 | 1,585,714 |
kWh
|
$0.16 | |
| Electricity Demand | $111,413 | 6,474 |
kW-mo/yr
|
$17.21 | |
| Electricity Fees | $1,389 | - |
|
- | |
| Natural Gas | $151,392 | 8,337 |
MMBtu
|
$18.16 | |
| Waste Disposal Costs | |||||
| Water Usage | $24,262 | 9,397 |
Tgal
|
$2.58 | |
| TOTAL YEARLY COSTS | $543,177 | ||||
| RECOMMENDED SAVINGS* | $349,734 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.3141: Use battery storage for demand control | $117,675 | $50,000 |
$49,905
309,586
kWh
|
$67,770
-
kW-mo/yr
|
- | |
| 02 | 2.9114: Use solar heat to make electricty | $92,259 | $619,600 |
$77,803
482,650
kWh
|
$14,456
-
kW-mo/yr
|
- | |
| 03 | 2.6231: Utilize controls to operate equipment only when needed | $15,348 | $2,000 |
$12,415
77,021
kWh
|
$2,933
-
kW-mo/yr
|
- | |
| 04 | 2.1321: Replace fossil fuel equipment with electrical equipment | $8,202 | $40,000 |
$8,202
50,877
kWh
|
- | - | |
| 05 | 2.4322: Use or replace with energy efficient substitutes | $112,267 | $176,800 |
$6,187
52,134
kWh
|
- | $106,080 | |
| 06 | 2.4322: Use or replace with energy efficient substitutes | $3,377 | $45,000 |
$3,377
10,890
kWh
|
- | - | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $606 | $1,600 |
$193
1,200
kWh
|
$413
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $349,734 | $935,000 |
$158,082
984,358
kWh
|
$85,572
-
kW-mo/yr
|
$106,080 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs