Assessment Year | 2022 |
---|---|
Principal Product | Outdoor Sporting Goods |
NAICS | 451110: Sporting Goods Stores |
SIC | 5941: Sporting Goods Stores and Bicycle Shops |
Sales Range | $100 M to 500M |
# of Employees | 316 |
Plant Area |
180,000
ft2
|
Annual Production | 1
units
|
Production Hrs. Annual | 4,004
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $234,380 | 3,678,704 |
kWh
|
$0.064 | |
Electricity Demand | $184,149 | 13,737 |
kW-mo/yr
|
$13.41 | |
Electricity Fees | $1,347 | - |
|
- | |
Natural Gas | $26,311 | 2,156 |
MMBtu
|
$12.20 | |
Waste Disposal Costs | |||||
Water Usage | $32,760 | 15,247 |
Tgal
|
$2.15 | |
Water Disposal | $9,813 | 15,247 |
Tgal
|
$0.64 | |
TOTAL YEARLY COSTS | $488,760 | ||||
RECOMMENDED SAVINGS* | $87,712 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.9114: Use solar heat to make electricty | $34,971 | $218,747 |
$15,146
237,776
kWh
|
$19,825
-
kW-mo/yr
|
- | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $33,110 | $75,225 |
$31,164
489,229
kWh
|
$1,946
-
kW-mo/yr
|
- | - | |
03 | 2.7134: Use photocell controls | $8,537 | $4,050 |
$2,666
41,859
kWh
|
$4,626
-
kW-mo/yr
|
$566 | $679 | |
04 | 2.4322: Use or replace with energy efficient substitutes | $4,843 | $8,200 |
$4,843
55,317
kWh
|
- | - | - | |
05 | 2.7262: Separate controls of air handlers from ac/ heating systems | $4,787 | $8,000 |
$4,787
75,150
kWh
|
- | - | - | |
06 | 2.7135: Install occupancy sensors | $1,464 | $2,000 |
$898
14,094
kWh
|
$566
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $87,712 | $316,222 |
$59,504
913,425
kWh
|
$26,963
-
kW-mo/yr
|
$566 | $679 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs