| Assessment Year | 2025 |
|---|---|
| Principal Product | Cooling Tower Fill, Eliminators, Louvers |
| NAICS | 326121: Unlaminated Plastics Profile Shape Manufacturing |
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 60 |
| Plant Area |
58,000
ft2
|
| Annual Production | 30,000
units
|
| Production Hrs. Annual | 5,460
hrs
|
| Location (State) | North Carolina |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $88,465 | 1,875,679 |
kWh
|
$0.047 |
| Electricity Demand | $88,366 | 7,123 |
kW-mo/yr
|
$12.41 |
| Electricity Fees | $26,917 | - |
|
- |
| Natural Gas | $14,792 | 1,190 |
MMBtu
|
$12.43 |
| TOTAL YEARLY COSTS | $218,540 | |||
| RECOMMENDED SAVINGS* | $22,913 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.2612: Use cooling tower water instead of refrigeration | $5,563 | $16,000 |
$3,947
83,980
kWh
|
$1,616
-
kW-mo/yr
|
|
| 02 | 2.6231: Utilize controls to operate equipment only when needed | $1,494 | $3,000 |
$1,494
31,784
kWh
|
- | |
| 03 | 2.2511: Insulate bare equipment | $13,610 | $9,048 |
$13,610
289,582
kWh
|
- | |
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,053 | $840 |
$2,053
43,680
kWh
|
- | |
| 05 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $193 | $570 |
$120
2,548
kWh
|
$73
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $22,913 | $29,458 |
$21,224
451,574
kWh
|
$1,689
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs