| Assessment Year | 2023 |
|---|---|
| Principal Product | food distribution |
| NAICS | 541614: Process, Physical Distribution, and Logistics Consulting Services |
| SIC | 4731: Arrangement of Transportation of Freight and Cargo |
| Sales Range | $50 M to 100M |
| # of Employees | 265 |
| Plant Area |
132,000
ft2
|
| Annual Production | 100,000,000
units
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | North Carolina |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $332,788 | 4,444,614 |
kWh
|
$0.075 |
| Electricity Demand | $36,791 | 8,160 |
kW-mo/yr
|
$4.51 |
| Electricity Fees | $7,014 | - |
|
- |
| Natural Gas | $52,303 | 4,837 |
MMBtu
|
$10.81 |
| TOTAL YEARLY COSTS | $428,896 | |||
| RECOMMENDED SAVINGS* | $120,611 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $30,247 | $40,000 |
$27,947
372,626
kWh
|
$2,300
-
kW-mo/yr
|
- | |
| 02 | 2.7442: Keep doors and windows shut when not on use | $31,058 | $23,000 | - | - |
$31,058
-
MMBtu
|
|
| 03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $6,613 | $2,800 |
$6,110
81,468
kWh
|
$503
-
kW-mo/yr
|
- | |
| 04 | 2.9114: Use solar heat to make electricty | $52,693 | $521,729 |
$52,693
702,579
kWh
|
- | - | |
| TOTAL RECOMMENDED | $120,611 | $587,529 |
$86,750
1,156,673
kWh
|
$2,803
-
kW-mo/yr
|
$31,058
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs