| Assessment Year | 2016 |
|---|---|
| Principal Product | Fastening Washers |
| NAICS | 332722: Bolt, Nut, Screw, Rivet, and Washer Manufacturing |
| SIC | 3452: Bolts, Nuts, Screws, Rivets, and Washers |
| Sales Range | $10 M to 50M |
| # of Employees | 50 |
| Plant Area |
90,000
ft2
|
| Annual Production | 240,000,000
pieces
|
| Production Hrs. Annual | 2,040
hrs
|
| Location (State) | Idaho |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $74,306 | 1,423,359 |
kWh
|
$0.052 | |
| Electricity Demand | $31,663 | 5,078 |
kW-mo/yr
|
$6.24 | |
| Electricity Fees | $2,684 | - |
|
- | |
| Natural Gas | $14,623 | 2,066 |
MMBtu
|
$7.08 | |
| Waste Disposal Costs | |||||
| Water Usage | $2,174 | 1,545 |
Tgal
|
$1.41 | |
| TOTAL YEARLY COSTS | $125,450 | ||||
| RECOMMENDED SAVINGS* | $6,470 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4221: Install compressor air intakes in coolest locations | $821 | $196 |
$821
15,719
kWh
|
- | - | - | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,699 | $982 |
$2,699
51,714
kWh
|
- | - | - | |
| 03 | 2.2437: Recover waste heat from equipment | $1,462 | $3,018 |
$(-152.0)
(-2,909)
kWh
|
- |
$1,614
-
MMBtu
|
- | |
| 04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $166 | $18 |
$85
1,641
kWh
|
$81
-
kW-mo/yr
|
- | - | |
| 05 | 2.6218: Turn off equipment when not in use | $90 | $22 |
$81
1,556
kWh
|
$9
-
kW-mo/yr
|
- | - | |
| 06 | 2.7224: Reduce space conditioning during non-working hours | $74 | $13 |
$4
79
kWh
|
- |
$70
-
MMBtu
|
- | |
| 07 | 2.7135: Install occupancy sensors | $648 | $184 |
$648
12,408
kWh
|
- | - | - | |
| 08 | 2.6211: Conserve energy by efficient use of vending machines | $75 | $166 |
$75
1,446
kWh
|
- | - | - | |
| 09 | 3.4151: Minimize water usage | $435 | $250 | - | - | - |
$435
-
Tgal
|
|
| TOTAL RECOMMENDED | $6,470 | $4,849 |
$4,261
81,654
kWh
|
$90
-
kW-mo/yr
|
$1,684
-
MMBtu
|
$435
-
Tgal
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs