| Assessment Year | 2015 |
|---|---|
| Principal Product | Doors |
| NAICS | 321911: Wood Window and Door Manufacturing |
| SIC | 2431: Millwork |
| Sales Range | $50 M to 100M |
| # of Employees | 340 |
| Plant Area |
243,000
ft2
|
| Annual Production | 416,000
pieces
|
| Production Hrs. Annual | 2,080
hrs
|
| Location (State) | Idaho |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $414,254 | 8,148,922 |
kWh
|
$0.051 |
| Electricity Demand | $141,231 | 21,053 |
kW-mo/yr
|
$6.71 |
| Electricity Fees | $3,497 | - |
|
- |
| Natural Gas | $91,383 | 12,461 |
MMBtu
|
$7.33 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $49,263 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4322: Use or replace with energy efficient substitutes | $656 | $3,871 |
$483
9,500
kWh
|
$173
-
kW-mo/yr
|
- | - | |
| 02 | 4.132: Purchase new equipment to reduce material use / cost | $2,499 | $3,000 | - | - | - | $2,499 | |
| 03 | 2.7135: Install occupancy sensors | $188 | $91 |
$188
3,693
kWh
|
- | - | - | |
| 04 | 2.7233: Use properly designed and sized hvac equipment | $652 | $2,825 |
$652
12,813
kWh
|
- | - | - | |
| 05 | 2.4322: Use or replace with energy efficient substitutes | $10,964 | $2,208 |
$8,496
167,104
kWh
|
$2,469
-
kW-mo/yr
|
- | - | |
| 06 | 2.4221: Install compressor air intakes in coolest locations | $1,643 | $1,314 |
$1,180
23,206
kWh
|
$463
-
kW-mo/yr
|
- | - | |
| 07 | 2.4235: Remove or close off unneeded compressed air lines | $71 | $711 |
$71
1,375
kWh
|
- | - | - | |
| 08 | 2.4224: Upgrade controls on compressors | $6,405 | $3,714 |
$4,135
81,334
kWh
|
$2,270
-
kW-mo/yr
|
- | - | |
| 09 | 2.2136: Install / repair insulation on steam lines | $5,322 | $4,102 | - | - |
$5,322
-
MMBtu
|
- | |
| 10 | 2.4322: Use or replace with energy efficient substitutes | $11,761 | $5,132 | - | - |
$11,761
-
MMBtu
|
- | |
| 11 | 2.6218: Turn off equipment when not in use | $9,102 | $145 |
$9,102
179,040
kWh
|
- | - | - | |
| TOTAL RECOMMENDED | $49,263 | $27,113 |
$24,307
478,065
kWh
|
$5,375
-
kW-mo/yr
|
$17,083
-
MMBtu
|
$2,499 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs