Assessment Year | 2015 |
---|---|
Principal Product | Modular Buildings |
NAICS | 321992: Prefabricated Wood Building Manufacturing |
SIC | 2452: Prefabricated Wood Buildings and Components |
Sales Range | $50 M to 100M |
# of Employees | 355 |
Plant Area |
160,000
ft2
|
Annual Production | 1,215
units
|
Production Hrs. Annual | 4,050
hrs
|
Location (State) | Idaho |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $85,413 | 1,564,471 |
kWh
|
$0.055 |
Electricity Demand | $29,121 | 5,328 |
kW-mo/yr
|
$5.47 |
Electricity Fees | $974 | - |
|
- |
Natural Gas | $87,465 | 12,129 |
MMBtu
|
$7.21 |
LPG | $32,661 | 1,642 |
MMBtu
|
$19.89 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $66,234 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | LPG Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $25,881 | $3,501 |
$21,169
387,720
kWh
|
$4,712
-
kW-mo/yr
|
- | - | - | |
02 | 2.4224: Upgrade controls on compressors | $3,691 | $5,780 |
$3,691
67,608
kWh
|
- | - | - | - | |
03 | 2.7224: Reduce space conditioning during non-working hours | $16,954 | $40 | - | - | - |
$16,954
-
MMBtu
|
- | |
04 | 2.7492: Use proper thickness of insulation on building envelope | $12,564 | $13,200 | - | - | - |
$12,564
-
MMBtu
|
- | |
05 | 2.7492: Use proper thickness of insulation on building envelope | $1,687 | $3,800 | - | - | - |
$1,687
-
MMBtu
|
- | |
06 | 2.7231: Use radiant heater for spot heating | $3,310 | $7,200 |
$(-12,265.0)
(-224,640)
kWh
|
- | - | - |
$15,575
-
MMBtu
|
|
07 | 2.8112: Combine utility meters | $810 | $1,587 | - | - | $810 | - | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,103 | $17,841 |
$866
15,856
kWh
|
$237
-
kW-mo/yr
|
- | - | - | |
09 | 2.7135: Install occupancy sensors | $48 | $92 |
$48
884
kWh
|
- | - | - | - | |
10 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $185 | $104 |
$143
2,623
kWh
|
$42
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $66,234 | $53,145 |
$13,652
250,051
kWh
|
$4,992
-
kW-mo/yr
|
$810 |
$31,205
-
MMBtu
|
$15,575
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | LPG Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs