Assessment Year | 2015 |
---|---|
Principal Product | Potatoes |
NAICS | 311411: Frozen Fruit, Juice, and Vegetable Manufacturing |
SIC | 2037: Frozen Fruits, Fruit Juices, and Vegetables |
Sales Range | $100 M to 500M |
# of Employees | 657 |
Plant Area |
332,800
ft2
|
Annual Production | 339,000,000
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Idaho |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $4,449,694 | 90,672,845 |
kWh
|
$0.049 |
Electricity Demand | $1,214,572 | 219,462 |
kW-mo/yr
|
$5.53 |
Electricity Fees | $125,840 | - |
|
- |
Natural Gas | $4,932,674 | 1,014,310 |
MMBtu
|
$4.86 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $644,168 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Water Consumption Savings | By-product Production Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.6242: Minimize operation of equipment maintained in standby condition | $394,723 | $180,080 | - | - |
$394,723
-
MMBtu
|
- | - | - | |
02 | 2.2626: Avoid frost formation on evaporators | $102,865 | $70,430 |
$(-18,956.6)
(-386,318)
kWh
|
- |
$22,436
-
MMBtu
|
$86,238
-
Tgal
|
$13,147
-
Tgal
|
- | |
03 | 2.1336: Install equipment to utilize waste fuel | $63,716 | $137,445 | - | - | - | - | - | $63,716 | |
04 | 2.4221: Install compressor air intakes in coolest locations | $41,557 | $1,388 |
$35,874
731,068
kWh
|
$5,683
-
kW-mo/yr
|
- | - | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $26,049 | $65,491 |
$22,563
459,812
kWh
|
$3,486
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,745 | $19,475 |
$4,170
84,972
kWh
|
$575
-
kW-mo/yr
|
- | - | - | - | |
07 | 2.7135: Install occupancy sensors | $6,168 | $801 |
$6,168
125,706
kWh
|
- | - | - | - | - | |
08 | 2.4133: Use most efficient type of electric motors | $2,284 | $7,380 |
$2,002
40,810
kWh
|
$282
-
kW-mo/yr
|
- | - | - | - | |
09 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,061 | $624 |
$2,061
41,992
kWh
|
- | - | - | - | - | |
TOTAL RECOMMENDED | $644,168 | $483,114 |
$53,881
1,098,042
kWh
|
$10,026
-
kW-mo/yr
|
$417,159
-
MMBtu
|
$86,238
-
Tgal
|
$13,147
-
Tgal
|
$63,716 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Water Consumption Savings | By-product Production Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs