| Assessment Year | 2014 |
|---|---|
| Principal Product | Office Furniture |
| NAICS | 337214: Office Furniture (except Wood) Manufacturing |
| SIC | 2522: Office Furniture, Except Wood |
| Sales Range | $50 M to 100M |
| # of Employees | 220 |
| Plant Area |
292,000
ft2
|
| Annual Production | 900,000
pieces
|
| Production Hrs. Annual | 4,016
hrs
|
| Location (State) | Idaho |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $341,466 | 5,961,900 |
kWh
|
$0.057 |
| Electricity Demand | $72,117 | 14,748 |
kW-mo/yr
|
$4.89 |
| Natural Gas | $198,377 | 31,683 |
MMBtu
|
$6.26 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $21,696 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.2511: Insulate bare equipment | $2,101 | $6,300 | - | - |
$2,101
-
MMBtu
|
- | |
| 02 | 2.4221: Install compressor air intakes in coolest locations | $1,095 | $620 |
$1,095
19,219
kWh
|
- | - | - | |
| 03 | 2.7243: Improve air circulation with destratification fans / other methods | $12,162 | $52,575 |
$12,162
213,380
kWh
|
- | - | - | |
| 04 | 2.7135: Install occupancy sensors | $1,312 | $313 |
$1,191
20,889
kWh
|
- | - | $121 | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $60 | $258 |
$60
1,060
kWh
|
- | - | - | |
| 06 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $387 | $600 |
$387
6,789
kWh
|
- | - | - | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,579 | $26,537 |
$3,486
61,167
kWh
|
$1,093
-
kW-mo/yr
|
- | - | |
| TOTAL RECOMMENDED | $21,696 | $87,203 |
$18,381
322,504
kWh
|
$1,093
-
kW-mo/yr
|
$2,101
-
MMBtu
|
$121 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs