Assessment Year | 2016 |
---|---|
Principal Product | Cookies, pies, and cakes |
NAICS | 311811: Retail Bakeries |
SIC | 2052: Cookies and Crackers |
Sales Range | $50 M to 100M |
# of Employees | 157 |
Plant Area |
135,000
ft2
|
Annual Production | 35,000,000
units
|
Production Hrs. Annual | 4,991
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $213,317 | 4,372,000 |
kWh
|
$0.049 | |
Electricity Demand | $28,896 | 4,816 |
kW-mo/yr
|
$6.00 | |
Electricity Fees | $409 | - |
|
- | |
Natural Gas | $119,222 | 30,949 |
MMBtu
|
$3.85 | |
Waste Disposal Costs | |||||
Water Usage | $10,631 | 2,812 |
Tgal
|
$3.78 | |
Water Disposal | $10,398 | 2,812 |
Tgal
|
$3.70 | |
TOTAL YEARLY COSTS | $382,873 | ||||
RECOMMENDED SAVINGS* | $35,329 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7231: Use radiant heater for spot heating | $17,520 | $1,900 |
$100
1,779
kWh
|
$4
-
kW-mo/yr
|
$17,416
-
MMBtu
|
|
02 | 2.1224: Replace boiler | $7,259 | $14,000 |
$(-11,340.0)
(-202,500)
kWh
|
$(-2,700.0)
-
kW-mo/yr
|
$21,299
-
MMBtu
|
|
03 | 2.1233: Analyze flue gas for proper air/fuel ratio | $3,620 | $6,000 | - | - |
$3,620
-
MMBtu
|
|
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,605 | $600 |
$2,104
37,565
kWh
|
$501
-
kW-mo/yr
|
- | |
05 | 2.3132: Recharge batteries on during off-peak demand periods | $2,280 | $50 | - |
$2,280
-
kW-mo/yr
|
- | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $932 | $20 |
$753
13,454
kWh
|
$179
-
kW-mo/yr
|
- | |
07 | 2.7135: Install occupancy sensors | $925 | $1,050 |
$627
11,195
kWh
|
$298
-
kW-mo/yr
|
- | |
08 | 2.4221: Install compressor air intakes in coolest locations | $188 | $500 |
$152
2,711
kWh
|
$36
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $35,329 | $24,120 |
$(-7,604.0)
(-135,796)
kWh
|
$598
-
kW-mo/yr
|
$42,335
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs