Assessment Year | 2016 |
---|---|
Principal Product | Printed paper goods |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 2752: Commercial Printing, Lithographic |
Sales Range | $5 M to 10M |
# of Employees | 48 |
Plant Area |
60,000
ft2
|
Annual Production | 1,400,000
lb
|
Production Hrs. Annual | 4,400
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $138,444 | 1,321,324 |
kWh
|
$0.10 |
Electricity Demand | $47,349 | 5,127 |
kW-mo/yr
|
$9.24 |
Electricity Fees | $420 | - |
|
- |
Natural Gas | $11,808 | 1,877 |
MMBtu
|
$6.29 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $26,166 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $21,959 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings | Primary Product Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,978 | $3,229 |
$3,953
37,715
kWh
|
$1,025
-
kW-mo/yr
|
- | - | - | - | |
02 | 2.7221: Lower temperature during the winter season and vice-versa | $2,345 | $15 | - | - |
$2,345
-
MMBtu
|
- | - | - | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,961 | $15 |
$1,581
15,085
kWh
|
$380
-
kW-mo/yr
|
- | - | - | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,217 | $1,000 |
$981
9,361
kWh
|
$236
-
kW-mo/yr
|
- | - | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,111 | $575 |
$733
6,991
kWh
|
$89
-
kW-mo/yr
|
- | $121 | $168 | - | |
06 | 2.4221: Install compressor air intakes in coolest locations | $784 | $900 |
$658
6,278
kWh
|
$126
-
kW-mo/yr
|
- | - | - | - | |
07 | 2.7135: Install occupancy sensors | $751 | $450 |
$552
5,266
kWh
|
$199
-
kW-mo/yr
|
- | - | - | - | |
08 | 4.513: Re-arrange equipment layout to reduce labor costs | $13,019 | $7,560 | - | - | - | $360 | - | $12,659 | |
TOTAL RECOMMENDED | $26,166 | $13,744 |
$8,458
80,696
kWh
|
$2,055
-
kW-mo/yr
|
$2,345
-
MMBtu
|
$481 | $168 | $12,659 | ||
TOTAL IMPLEMENTED | $21,959 | $12,704 |
$7,173
68,439
kWh
|
$1,767
-
kW-mo/yr
|
- | $360 | - | $12,659 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings | Primary Product Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs