Assessment Year | 2015 |
---|---|
Principal Product | Circuit Boards |
NAICS | 334418: Printed Circuit Assembly (Electronic Assembly) Manufacturing |
SIC | 3679: Electronic Components, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 120 |
Plant Area |
60,000
ft2
|
Annual Production | 1,000,000
pieces
|
Production Hrs. Annual | 4,810
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $107,645 | 2,192,003 |
kWh
|
$0.049 |
Electricity Demand | $20,657 | 4,641 |
kW-mo/yr
|
$4.45 |
Electricity Fees | $2,399 | - |
|
- |
Natural Gas | $12,385 | 1,594 |
MMBtu
|
$7.77 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $40,245 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $22,860 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7232: Replace existing hvac unit with high efficiency model | $15,619 | $115,000 |
$13,815
281,360
kWh
|
- |
$1,804
-
MMBtu
|
- | - | - | |
02 | 2.7243: Improve air circulation with destratification fans / other methods | $8,131 | $1,000 | - | - |
$8,131
-
MMBtu
|
- | - | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,753 | $8,550 |
$3,877
81,840
kWh
|
$876
-
kW-mo/yr
|
- | - | - | - | |
04 | 2.4314: Use synthetic lubricant | $3,554 | $500 |
$2,674
54,470
kWh
|
$880
-
kW-mo/yr
|
- | - | - | - | |
05 | 2.7134: Use photocell controls | $1,020 | $500 |
$647
13,175
kWh
|
$230
-
kW-mo/yr
|
- | - | $90 | $53 | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $586 | $20 |
$478
9,736
kWh
|
$108
-
kW-mo/yr
|
- | - | - | - | |
07 | 2.4221: Install compressor air intakes in coolest locations | $585 | $250 |
$501
10,211
kWh
|
$84
-
kW-mo/yr
|
- | - | - | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $447 | $470 |
$229
4,660
kWh
|
$28
-
kW-mo/yr
|
- | - | $81 | $109 | |
09 | 2.7135: Install occupancy sensors | $349 | $375 |
$288
5,868
kWh
|
$61
-
kW-mo/yr
|
- | - | - | - | |
10 | 2.3132: Recharge batteries on during off-peak demand periods | $160 | $20 | - |
$160
-
kW-mo/yr
|
- | - | - | - | |
11 | 3.5315: Lease / purchase baler; sell cardboard to recycler | $5,040 | $6,500 | - | - | - |
$5,040
-
lb
|
- | - | |
TOTAL RECOMMENDED | $40,245 | $133,185 |
$22,510
461,320
kWh
|
$2,427
-
kW-mo/yr
|
$9,935
-
MMBtu
|
$5,040
-
lb
|
$171 | $162 | ||
TOTAL IMPLEMENTED | $22,860 | $17,645 |
$7,570
157,049
kWh
|
$1,929
-
kW-mo/yr
|
$8,131
-
MMBtu
|
$5,040
-
lb
|
$81 | $109 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs