Assessment Year | 2013 |
---|---|
Principal Product | Electrical cabinets |
NAICS | 332439: Other Metal Container Manufacturing |
SIC | 3499: Fabricated Metal Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 57 |
Plant Area |
52,000
ft2
|
Annual Production | 4,000
pieces
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $59,449 | 1,057,700 |
kWh
|
$0.056 |
Electricity Demand | $51,664 | 3,780 |
kW-mo/yr
|
$13.67 |
Electricity Fees | $408 | - |
|
- |
Natural Gas | $38,772 | 7,737 |
MMBtu
|
$5.01 |
LPG | $3,209 | 109 |
MMBtu
|
$29.39 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $17,330 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $12,975 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | LPG Savings |
---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $12,975 | $200 |
$7,653
151,845
kWh
|
$5,322
-
kW-mo/yr
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,306 | $5,680 |
$760
14,318
kWh
|
$546
-
kW-mo/yr
|
- | |
03 | 2.3132: Recharge batteries on during off-peak demand periods | $1,152 | $30 | - |
$1,152
-
kW-mo/yr
|
- | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $666 | $25 |
$393
7,799
kWh
|
$273
-
kW-mo/yr
|
- | |
05 | 2.8227: Adjust / maintain fork lift trucks for most efficient operation | $651 | $2,300 |
$(-2,558.0)
(-50,752)
kWh
|
- |
$3,209
-
MMBtu
|
|
06 | 2.4133: Use most efficient type of electric motors | $354 | $440 |
$138
2,735
kWh
|
$216
-
kW-mo/yr
|
- | |
07 | 2.4221: Install compressor air intakes in coolest locations | $226 | $700 |
$133
2,642
kWh
|
$93
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $17,330 | $9,375 |
$6,519
128,587
kWh
|
$7,602
-
kW-mo/yr
|
$3,209
-
MMBtu
|
||
TOTAL IMPLEMENTED | $12,975 | $200 |
$7,653
151,845
kWh
|
$5,322
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | LPG Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs