Assessment Year | 2012 |
---|---|
Principal Product | Treated railroad ties |
NAICS | 321114: Wood Preservation |
SIC | 2491: Wood Preserving |
Sales Range | $10 M to 50M |
# of Employees | 80 |
Plant Area |
250,000
ft2
|
Annual Production | 5,800
thousand feet
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $190,319 | 3,236,455 |
kWh
|
$0.059 |
Electricity Demand | $46,929 | 8,086 |
kW-mo/yr
|
$5.80 |
Electricity Fees | $14,642 | - |
|
- |
Natural Gas | $418,951 | 61,520 |
MMBtu
|
$6.81 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $162,911 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $52,208 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.1213: Direct warmest air to combustion intake | $78,417 | $20,000 | - | - |
$78,417
-
MMBtu
|
- | - | |
02 | 2.1222: Install turbulators | $28,818 | $1,500 | - | - |
$28,818
-
MMBtu
|
- | - | |
03 | 2.4133: Use most efficient type of electric motors | $24,920 | $28,550 |
$21,116
359,116
kWh
|
$3,804
-
kW-mo/yr
|
- | - | - | |
04 | 2.4221: Install compressor air intakes in coolest locations | $9,753 | $2,000 |
$8,592
146,122
kWh
|
$1,161
-
kW-mo/yr
|
- | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,606 | $19,440 |
$4,617
78,511
kWh
|
$989
-
kW-mo/yr
|
- | - | - | |
06 | 2.7111: Reduce illumination to minimum necessary levels | $3,468 | $1,965 |
$3,315
47,304
kWh
|
- | - | $4 | $149 | |
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,275 | $20 |
$2,885
49,070
kWh
|
$390
-
kW-mo/yr
|
- | - | - | |
08 | 2.7135: Install occupancy sensors | $3,023 | $975 |
$2,772
47,139
kWh
|
$251
-
kW-mo/yr
|
- | - | - | |
09 | 2.7134: Use photocell controls | $4,708 | $540 |
$3,781
64,309
kWh
|
$777
-
kW-mo/yr
|
- | $70 | $80 | |
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $540 | $1,239 |
$429
7,288
kWh
|
$111
-
kW-mo/yr
|
- | - | - | |
11 | 2.2136: Install / repair insulation on steam lines | $383 | $650 | - | - |
$383
-
MMBtu
|
- | - | |
TOTAL RECOMMENDED | $162,911 | $76,879 |
$47,507
798,859
kWh
|
$7,483
-
kW-mo/yr
|
$107,618
-
MMBtu
|
$74 | $229 | ||
TOTAL IMPLEMENTED | $52,208 | $53,414 |
$44,192
751,555
kWh
|
$7,483
-
kW-mo/yr
|
$383
-
MMBtu
|
$70 | $80 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs