Assessment Year | 2012 |
---|---|
Principal Product | Automotive vapor canisters |
NAICS | 336310: Motor Vehicle Gasoline Engine and Engine Parts Manufacturing |
SIC | 3714: Motor Vehicle Parts and Accessories |
Sales Range | $10 M to 50M |
# of Employees | 107 |
Plant Area |
80,000
ft2
|
Annual Production | 1,500,000
pieces
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $277,200 | 4,829,090 |
kWh
|
$0.057 |
Electricity Demand | $54,528 | 9,730 |
kW-mo/yr
|
$5.60 |
Electricity Fees | $1,420 | - |
|
- |
Natural Gas | $10,900 | 1,726 |
MMBtu
|
$6.32 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $34,429 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,670 | $30,287 |
$10,957
190,883
kWh
|
$1,713
-
kW-mo/yr
|
|
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,041 | $6,000 |
$3,494
60,873
kWh
|
$547
-
kW-mo/yr
|
|
03 | 2.7135: Install occupancy sensors | $4,980 | $1,050 |
$4,451
77,538
kWh
|
$529
-
kW-mo/yr
|
|
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,859 | $20 |
$4,202
73,205
kWh
|
$657
-
kW-mo/yr
|
|
05 | 2.4314: Use synthetic lubricant | $4,093 | $1,200 |
$3,540
61,672
kWh
|
$553
-
kW-mo/yr
|
|
06 | 2.4221: Install compressor air intakes in coolest locations | $2,988 | $2,000 |
$2,584
45,019
kWh
|
$404
-
kW-mo/yr
|
|
07 | 2.3132: Recharge batteries on during off-peak demand periods | $798 | $40 | - |
$798
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $34,429 | $40,597 |
$29,228
509,190
kWh
|
$5,201
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs