Assessment Year | 2011 |
---|---|
Principal Product | Specialty Chmicals |
NAICS | 325199: All Other Basic Organic Chemical Manufacturing |
SIC | 2869: Industrial Organic Chemicals, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 76 |
Plant Area |
17,000
ft2
|
Annual Production | 114,000,000
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $869,657 | 19,891,076 |
kWh
|
$0.044 |
Electricity Demand | $77,457 | 32,762 |
kW-mo/yr
|
$2.36 |
Electricity Fees | $86,261 | - |
|
- |
Natural Gas | $417,907 | 62,372 |
MMBtu
|
$6.70 |
Other Energy | $2,293,784 | 172,709 |
MMBtu
|
$13.28 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $407,450 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $29,551 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Energy Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $25,233 | $21,500 |
$23,495
537,642
kWh
|
$1,738
-
kW-mo/yr
|
- | - | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,457 | $3,064 |
$2,288
52,356
kWh
|
$169
-
kW-mo/yr
|
- | - | - | |
03 | 2.7135: Install occupancy sensors | $1,861 | $600 |
$1,719
39,330
kWh
|
$142
-
kW-mo/yr
|
- | - | - | |
04 | 2.4221: Install compressor air intakes in coolest locations | $1,318 | $200 |
$1,227
28,076
kWh
|
$91
-
kW-mo/yr
|
- | - | - | |
05 | 3.4151: Minimize water usage | $2,025 | $1,600 | - | - | - | - |
$2,025
-
Tgal
|
|
06 | 2.1392: Replace purchased steam with other energy source | $374,556 | $995,000 | - | - |
$(-1,919,228.0)
-
MMBtu
|
$2,293,784
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $407,450 | $1,021,964 |
$28,729
657,404
kWh
|
$2,140
-
kW-mo/yr
|
$(-1,919,228.0)
-
MMBtu
|
$2,293,784
-
MMBtu
|
$2,025
-
Tgal
|
||
TOTAL IMPLEMENTED | $29,551 | $25,164 |
$27,502
629,328
kWh
|
$2,049
-
kW-mo/yr
|
- | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Energy Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs