Assessment Year | 2008 |
---|---|
Principal Product | water and Natural Gas Flow Products |
NAICS | 331529: Other Nonferrous Metal Foundries (except Die-Casting) |
SIC | 3366: Copper Foundries |
Sales Range | $1 M to 5M |
# of Employees | 300 |
Plant Area |
280,000
ft2
|
Annual Production | 10,000,000
units
|
Production Hrs. Annual | 2,600
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,332,125 | 27,439,179 |
kWh
|
$0.049 |
Electricity Demand | $105,962 | 68,203 |
kW-mo/yr
|
$1.55 |
Electricity Fees | $114,536 | - |
|
- |
Natural Gas | $637,212 | 78,255 |
MMBtu
|
$8.14 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $201,468 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $133,665 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Primary Raw Material Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $84,447 | $2,972 |
$82,386
1,452,995
kWh
|
$2,061
-
kW-mo/yr
|
- | - | - | |
02 | 2.7135: Install occupancy sensors | $1,472 | $676 |
$1,432
25,249
kWh
|
$40
-
kW-mo/yr
|
- | - | - | |
03 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $4,548 | $4,569 |
$3,344
58,979
kWh
|
$124
-
kW-mo/yr
|
- | $831 | $249 | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $893 | $1,366 |
$569
10,038
kWh
|
$14
-
kW-mo/yr
|
- | $130 | $180 | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $48,385 | $10,001 |
$47,298
834,183
kWh
|
$1,087
-
kW-mo/yr
|
- | - | - | |
06 | 2.4221: Install compressor air intakes in coolest locations | $833 | $501 |
$722
12,744
kWh
|
$111
-
kW-mo/yr
|
- | - | - | |
07 | 2.1224: Replace boiler | $37,675 | $65,001 | - | - |
$37,675
-
MMBtu
|
- | - | |
08 | 2.1213: Direct warmest air to combustion intake | $4,096 | $1,251 | - | - |
$4,096
-
MMBtu
|
- | - | |
09 | 2.7231: Use radiant heater for spot heating | $19,119 | $14,001 | - | - |
$19,119
-
MMBtu
|
- | - | |
TOTAL RECOMMENDED | $201,468 | $100,338 |
$135,751
2,394,188
kWh
|
$3,437
-
kW-mo/yr
|
$60,890
-
MMBtu
|
$961 | $429 | ||
TOTAL IMPLEMENTED | $133,665 | $13,474 |
$130,406
2,299,922
kWh
|
$3,259
-
kW-mo/yr
|
- | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Primary Raw Material Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs