Assessment Year | 2006 |
---|---|
Principal Product | Wood Crates |
NAICS | 321999: All Other Miscellaneous Wood Product Manufacturing |
SIC | 2448: Wood Pallets and Skids |
Sales Range | $5 M to 10M |
# of Employees | 107 |
Plant Area |
55,000
ft2
|
Annual Production | 561,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $39,764 | 745,920 |
kWh
|
$0.053 |
Electricity Demand | $4,460 | 1,880 |
kW-mo/yr
|
$2.37 |
Natural Gas | $12,723 | 1,629 |
MMBtu
|
$7.81 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $11,255 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $10,390 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7231: Use radiant heater for spot heating | $4,173 | $2 | - | - |
$4,173
-
MMBtu
|
- | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,537 | $600 |
$3,258
61,130
kWh
|
$279
-
kW-mo/yr
|
- | - | |
03 | 2.4314: Use synthetic lubricant | $805 | $300 |
$742
13,937
kWh
|
$63
-
kW-mo/yr
|
- | - | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $577 | - |
$532
9,988
kWh
|
$45
-
kW-mo/yr
|
- | - | |
05 | 2.4221: Install compressor air intakes in coolest locations | $267 | $500 |
$246
4,621
kWh
|
$21
-
kW-mo/yr
|
- | - | |
06 | 2.7111: Reduce illumination to minimum necessary levels | $1,368 | $90 |
$1,289
24,178
kWh
|
$79
-
kW-mo/yr
|
- | - | |
07 | 2.7135: Install occupancy sensors | $288 | $225 |
$260
4,885
kWh
|
$28
-
kW-mo/yr
|
- | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $240 | $250 |
$142
2,655
kWh
|
$9
-
kW-mo/yr
|
- | $89 | |
TOTAL RECOMMENDED | $11,255 | $1,967 |
$6,469
121,394
kWh
|
$524
-
kW-mo/yr
|
$4,173
-
MMBtu
|
$89 | ||
TOTAL IMPLEMENTED | $10,390 | $1,742 |
$5,677
106,521
kWh
|
$451
-
kW-mo/yr
|
$4,173
-
MMBtu
|
$89 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |