Assessment Year | 2004 |
---|---|
Principal Product | Metal Stampings |
NAICS | 336390: Other Motor Vehicle Parts Manufacturing |
SIC | 3714: Motor Vehicle Parts and Accessories |
Sales Range | $5 M to 10M |
# of Employees | 110 |
Plant Area |
69,000
ft2
|
Annual Production | 10,000,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $82,691 | 1,458,110 |
kWh
|
$0.057 |
Electricity Demand | $10,558 | 4,482 |
kW-mo/yr
|
$2.36 |
Natural Gas | $15,358 | 2,221 |
MMBtu
|
$6.91 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $34,883 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $24,314 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Primary Raw Material Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7447: Install vinyl strip / high speed / air curtain doors | $5,490 | $24,000 | - | - |
$5,490
-
MMBtu
|
- | - | - | |
02 | 2.4133: Use most efficient type of electric motors | $4,379 | $8,800 |
$4,132
72,867
kWh
|
$247
-
kW-mo/yr
|
- | - | - | - | |
03 | 2.7231: Use radiant heater for spot heating | $3,970 | $3,000 | - | - |
$3,970
-
MMBtu
|
- | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,012 | $3,900 |
$2,653
46,800
kWh
|
$212
-
kW-mo/yr
|
- | - | $147 | - | |
05 | 2.2449: Recover heat from exhausted steam, hot air or hot water | $2,571 | $1,000 | - | - |
$2,571
-
MMBtu
|
- | - | - | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,261 | - |
$2,063
36,386
kWh
|
$198
-
kW-mo/yr
|
- | - | - | - | |
07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,114 | $3,100 |
$1,997
35,195
kWh
|
$117
-
kW-mo/yr
|
- | - | - | - | |
08 | 2.7135: Install occupancy sensors | $609 | $1,056 |
$502
8,875
kWh
|
$107
-
kW-mo/yr
|
- | - | - | - | |
09 | 3.4115: Recover and reuse cooling water | $9,977 | $6,000 | - | - | - |
$9,977
-
Tgal
|
- | - | |
10 | 4.821: Pay bills on time to avoid late fees | $500 | - | - | - | - | - | - | $500 | |
TOTAL RECOMMENDED | $34,883 | $50,856 |
$11,347
200,123
kWh
|
$881
-
kW-mo/yr
|
$12,031
-
MMBtu
|
$9,977
-
Tgal
|
$147 | $500 | ||
TOTAL IMPLEMENTED | $24,314 | $22,800 |
$10,845
191,248
kWh
|
$774
-
kW-mo/yr
|
$2,571
-
MMBtu
|
$9,977
-
Tgal
|
$147 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Primary Raw Material Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs