Assessment Year | 2004 |
---|---|
Principal Product | PVC Plastic Dip & Injection Molded Products |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 85 |
Plant Area |
85,000
ft2
|
Annual Production | 400,000,000
pieces
|
Production Hrs. Annual | 5,000
hrs
|
Location (State) | Missouri |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $94,977 | 1,471,050 |
kWh
|
$0.065 |
Electricity Demand | $9,386 | 4,392 |
kW-mo/yr
|
$2.14 |
Natural Gas | $49,008 | 6,928 |
MMBtu
|
$7.07 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $7,540 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $5,293 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Primary Raw Material Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7135: Install occupancy sensors | $2,506 | $2,025 |
$2,048
41,117
kWh
|
$458
-
kW-mo/yr
|
- | - | - | |
02 | 2.7135: Install occupancy sensors | $953 | $2,175 |
$1,082
21,779
kWh
|
$37
-
kW-mo/yr
|
$(-166.0) | - | - | |
03 | 2.4133: Use most efficient type of electric motors | $952 | $1,280 |
$928
18,645
kWh
|
$24
-
kW-mo/yr
|
- | - | - | |
04 | 2.4221: Install compressor air intakes in coolest locations | $611 | $600 |
$544
10,924
kWh
|
$67
-
kW-mo/yr
|
- | - | - | |
05 | 2.7111: Reduce illumination to minimum necessary levels | $575 | $24 |
$440
7,570
kWh
|
$36
-
kW-mo/yr
|
$6 | - | $93 | |
06 | 2.7144: Install spectral reflectors / delamp | $271 | $335 |
$166
3,329
kWh
|
$10
-
kW-mo/yr
|
$15 | - | $80 | |
07 | 3.1162: Use less wasteful packaging | $1,672 | $180 | - | - | - | $1,672 | - | |
TOTAL RECOMMENDED | $7,540 | $6,619 |
$5,208
103,364
kWh
|
$632
-
kW-mo/yr
|
$(-145.0) | $1,672 | $173 | ||
TOTAL IMPLEMENTED | $5,293 | $6,415 |
$4,768
95,794
kWh
|
$596
-
kW-mo/yr
|
$(-151.0) | - | $80 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Primary Raw Material Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs