Assessment Year | 1996 |
---|---|
Principal Product | Paper Products |
NAICS |
n/a
|
SIC | 2671: Packaging Paper and Plastics Film, Coated and Laminated |
Sales Range | $10 M to 50M |
# of Employees | 89 |
Plant Area |
98,940
ft2
|
Annual Production | 2,160,000,000
thousand feet
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $120,662 | 3,892,732 |
kWh
|
$0.031 |
Electricity Demand | $88,928 | 6,973 |
kW-mo/yr
|
$12.75 |
Electricity Fees | $2,852 | - |
|
- |
Natural Gas | $146,661 | 39,887 |
MMBtu
|
$3.68 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $27,964 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $13,965 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Ancillary Material Cost Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $7,122 | $12,270 |
$4,754
153,283
kWh
|
$2,368
-
kW-mo/yr
|
- | - | - | |
02 | 2.4221: Install compressor air intakes in coolest locations | $2,590 | $800 |
$1,548
49,824
kWh
|
$1,042
-
kW-mo/yr
|
- | - | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,611 | $2,563 |
$856
27,550
kWh
|
$755
-
kW-mo/yr
|
- | - | - | |
04 | 2.7135: Install occupancy sensors | $1,441 | $1,500 |
$551
17,878
kWh
|
$890
-
kW-mo/yr
|
- | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,531 | $2,590 |
$773
24,912
kWh
|
$510
-
kW-mo/yr
|
$34 | $214 | - | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,111 | $1,020 |
$742
24,033
kWh
|
$369
-
kW-mo/yr
|
- | - | - | |
07 | 2.7243: Improve air circulation with destratification fans / other methods | $562 | $660 | - |
$562
-
kW-mo/yr
|
- | - | - | |
08 | 3.3122: Use filtration, centrifuging to remove contaminants | $11,996 | $9,045 |
$(-350.0)
(-11,430)
kWh
|
- | $1,680 | - |
$10,666
-
Tgal
|
|
TOTAL RECOMMENDED | $27,964 | $30,448 |
$8,874
286,050
kWh
|
$6,496
-
kW-mo/yr
|
$1,714 | $214 |
$10,666
-
Tgal
|
||
TOTAL IMPLEMENTED | $13,965 | $19,243 |
$8,673
279,602
kWh
|
$5,044
-
kW-mo/yr
|
$34 | $214 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Ancillary Material Cost Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs