Assessment Year | 1996 |
---|---|
Principal Product | Hydraulic door closers |
NAICS |
n/a
|
SIC | 3429: Hardware, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 360 |
Plant Area |
177,886
ft2
|
Annual Production | 1,000,000
pieces
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $326,692 | 6,533,705 |
kWh
|
$0.050 |
Electricity Demand | $18,348 | 28,634 |
kW-mo/yr
|
$0.64 |
Electricity Fees | $69,075 | - |
|
- |
Natural Gas | $95,631 | 29,296 |
MMBtu
|
$3.26 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $107,958 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $34,091 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Other Liquid (non-haz) Savings | Solid Waste (non-haz) Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $34,399 | $31,000 |
$40,283
657,386
kWh
|
$4,114
-
kW-mo/yr
|
$(-9,998.0)
-
MMBtu
|
- | - | - | |
02 | 2.4133: Use most efficient type of electric motors | $15,921 | $36,930 |
$15,563
322,098
kWh
|
$358
-
kW-mo/yr
|
- | - | - | - | |
03 | 2.7135: Install occupancy sensors | $4,119 | $2,550 |
$4,022
83,236
kWh
|
$97
-
kW-mo/yr
|
- | - | - | - | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,521 | $60 |
$1,498
31,067
kWh
|
$23
-
kW-mo/yr
|
- | - | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,301 | $5,169 |
$1,251
25,791
kWh
|
$50
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.4221: Install compressor air intakes in coolest locations | $487 | $750 |
$477
9,965
kWh
|
$10
-
kW-mo/yr
|
- | - | - | - | |
07 | 3.4113: Treat and reuse rinse waters | $29,772 | $60,000 | - | - | - |
$29,772
-
Tgal
|
- | - | |
08 | 3.2123: Convert to high volume low pressure (hvlp) paint guns | $11,229 | $650 | - | - | - | - |
$11,229
-
gal
|
- | |
09 | 3.5316: Contract a wood pallet recycling company | $5,349 | $370 | - | - | - | - | - |
$5,349
-
lb
|
|
10 | 3.4115: Recover and reuse cooling water | $3,860 | $8,200 | - | - | - |
$3,860
-
Tgal
|
- | - | |
TOTAL RECOMMENDED | $107,958 | $145,679 |
$63,094
1,129,543
kWh
|
$4,652
-
kW-mo/yr
|
$(-9,998.0)
-
MMBtu
|
$33,632
-
Tgal
|
$11,229
-
gal
|
$5,349
-
lb
|
||
TOTAL IMPLEMENTED | $34,091 | $45,359 |
$22,334
462,192
kWh
|
$528
-
kW-mo/yr
|
- | - |
$11,229
-
gal
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Other Liquid (non-haz) Savings | Solid Waste (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs