Assessment Year | 1988 |
---|---|
Principal Product | UNFINISHED CLOTH |
NAICS |
n/a
|
SIC | 2211: Broadwoven Fabric Mills, Cotton |
Sales Range | $10 M to 50M |
# of Employees | 242 |
Plant Area |
n/a
|
Annual Production | 57,720
thousand feet
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $811,087 | 17,718,054 |
kWh
|
$0.046 |
Natural Gas | $83,300 | 27,916 |
MMBtu
|
$2.98 |
Fuel Oil #6 | $17,240 | 5,375 |
MMBtu
|
$3.21 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $193,284 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $167,809 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Fuel Oil #6 Savings |
---|---|---|---|---|---|---|---|
01 | 2.7226: Use computer programs to optimize hvac performance | $110,478 | $13,800 |
$110,478
2,412,661
kWh
|
- | - | |
02 | 2.4133: Use most efficient type of electric motors | $8,033 | $2,092 |
$8,033
175,557
kWh
|
- | - | |
03 | 2.7111: Reduce illumination to minimum necessary levels | $24,038 | $8,425 |
$24,038
524,912
kWh
|
- | - | |
04 | 2.7122: Disconnect ballasts | $2,498 | $500 |
$2,498
54,513
kWh
|
- | - | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $15,175 | - |
$15,175
333,236
kWh
|
- | - | |
06 | 2.4312: Improve lubrication practices | $1,362 | - |
$1,362
29,894
kWh
|
- | - | |
07 | 2.2692: Use outside cold water source as a supply of cooling water | $24,113 | $18,600 |
$24,113
526,671
kWh
|
- | - | |
08 | 2.1233: Analyze flue gas for proper air/fuel ratio | $6,202 | $6,000 | - |
$5,138
-
MMBtu
|
$1,064
-
MMBtu
|
|
09 | 2.4221: Install compressor air intakes in coolest locations | $1,385 | $1,600 |
$1,385
30,188
kWh
|
- | - | |
TOTAL RECOMMENDED | $193,284 | $51,017 |
$187,082
4,087,632
kWh
|
$5,138
-
MMBtu
|
$1,064
-
MMBtu
|
||
TOTAL IMPLEMENTED | $167,809 | $32,417 |
$161,607
3,531,067
kWh
|
$5,138
-
MMBtu
|
$1,064
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Fuel Oil #6 Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs