Assessment Year | 1987 |
---|---|
Principal Product | SHEET METAL PRODUCTS |
NAICS |
n/a
|
SIC | 3444: Sheet Metal Work |
Sales Range | $1 M to 5M |
# of Employees | 70 |
Plant Area |
n/a
|
Annual Production | 700
ton
|
Production Hrs. Annual | 2,340
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $44,797 | 671,161 |
kWh
|
$0.067 |
Natural Gas | $6,269 | 1,030 |
MMBtu
|
$6.09 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $22,994 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $20,453 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $16,207 | $5,000 |
$21,273
249,707
kWh
|
$(-5,066.0)
-
MMBtu
|
- | |
02 | 2.3191: Use demand controller or load shedder | $2,078 | $500 |
$2,078
-
kWh
|
- | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,247 | $3,793 |
$2,247
33,705
kWh
|
- | - | |
04 | 2.6212: Turn off equipment during breaks, reduce operating time | $716 | $300 |
$156
2,345
kWh
|
$560
-
MMBtu
|
- | |
05 | 2.7226: Use computer programs to optimize hvac performance | $763 | $500 |
$763
11,430
kWh
|
- | - | |
06 | 2.1123: Install automatic stack damper | $346 | $800 | - |
$346
-
MMBtu
|
- | |
07 | 2.4133: Use most efficient type of electric motors | $103 | $195 |
$103
1,465
kWh
|
- | - | |
08 | 2.4321: Upgrade obsolete equipment | $200 | - |
$450
6,741
kWh
|
- | $(-250.0) | |
09 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $117 | - |
$117
1,758
kWh
|
- | - | |
10 | 2.4221: Install compressor air intakes in coolest locations | $117 | $200 |
$117
1,758
kWh
|
- | - | |
11 | 2.6121: Reduce hot water temperature to the minimum required | $100 | - | - |
$100
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $22,994 | $11,288 |
$27,304
308,909
kWh
|
$(-4,060.0)
-
MMBtu
|
$(-250.0) | ||
TOTAL IMPLEMENTED | $20,453 | $9,988 |
$25,109
307,151
kWh
|
$(-4,406.0)
-
MMBtu
|
$(-250.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs