ITAC Assessment: AS0494
ITAC logo
ITAC Assessment: AS0494
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2021
Principal Product Treated Wastewater
NAICS 221320: Sewage Treatment Facilities
SIC 4952: Sewerage Systems
Sales Range less than $500
k
# of Employees 10
Plant Area 50,000
ft2
Annual Production 1,348,000
Tgal
Production Hrs. Annual 8,760
hrs
Location (State) Arizona

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $230,885 5,359,789
kWh
Electricity Demand $211,287 11,220
kW-mo/yr
Electricity Fees $38,193 -
Natural Gas $64,089 10,914
MMBtu
TOTAL YEARLY COSTS $544,454
RECOMMENDED SAVINGS* $153,862 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $153,636

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings One-time Revenue or Avoided Cost Savings
01 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $130,212 $564 $49,706
1,155,948
kWh
$80,506
-
kW-mo/yr
-
02 2.7142: Utilize higher efficiency lamps and/or ballasts $12,021 $31,867 $8,287
192,732
kWh
$4,935
-
kW-mo/yr
$(-1,201.0)
03 2.6125: Keep equipment clean $3,890 $2,174 $3,890
96,490
kWh
- -
04 2.7135: Install occupancy sensors $3,827 $2,905 $3,827
89,005
kWh
- -
05 2.8112: Combine utility meters $3,107 $1,473 $(-8,921.0)
-
kWh
$9,849
-
kW-mo/yr
$2,179
06 2.4221: Install compressor air intakes in coolest locations $518 $382 $337
7,840
kWh
$181
-
kW-mo/yr
-
07 2.6211: Conserve energy by efficient use of vending machines $226 $354 $139
3,229
kWh
$87
-
kW-mo/yr
-
08 2.7272: Install heat pipes / raise cooling setpoint $61 $47 $38
891
kWh
$23
-
kW-mo/yr
-
TOTAL RECOMMENDED $153,862 $39,766 $57,303
1,546,135
kWh
$95,581
-
kW-mo/yr
$978
TOTAL IMPLEMENTED $153,636 $39,412 $57,164
1,542,906
kWh
$95,494
-
kW-mo/yr
$978
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings One-time Revenue or Avoided Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs