| Assessment Year | 2005 |
|---|---|
| Principal Product | Wlak-in coolers |
| NAICS | 333415: Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipmen |
| SIC | 3585: Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment |
| Sales Range | $10 M to 50M |
| # of Employees | 90 |
| Plant Area |
45,000
ft2
|
| Annual Production | 2,600,000
thousand feet
|
| Production Hrs. Annual | 4,182
hrs
|
| Location (State) | Arizona |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $78,912 | 1,276,080 |
kWh
|
$0.062 |
| Electricity Demand | $4,089 | 2,571 |
kW-mo/yr
|
$1.59 |
| Electricity Fees | $5,657 | - |
|
- |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $98,064 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $9,562 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Primary Product Savings |
|---|---|---|---|---|---|---|---|
| 01 | 4.445: Install equipment to move product | $55,760 | $2,000 | - | - | $55,760 | |
| 02 | 4.448: Install automatic part storage / retreval system | $29,744 | $15,000 | - | - | $29,744 | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,557 | $210 |
$3,314
54,165
kWh
|
$243
-
kW-mo/yr
|
- | |
| 04 | 2.2622: Replace existing chiller with high efficiency model | $2,674 | $5,500 |
$2,380
38,893
kWh
|
$294
-
kW-mo/yr
|
- | |
| 05 | 2.7124: Make a practice of turning off lights when not needed | $2,250 | $12,278 |
$2,073
33,873
kWh
|
$177
-
kW-mo/yr
|
- | |
| 06 | 2.4239: Eliminate or reduce compressed air usage | $1,527 | $70 |
$1,527
24,950
kWh
|
- | - | |
| 07 | 2.7124: Make a practice of turning off lights when not needed | $1,152 | $1,260 |
$1,152
18,819
kWh
|
- | - | |
| 08 | 2.4226: Use / purchase optimum sized compressor | $968 | $3,000 |
$886
8,084
kWh
|
$82
-
kW-mo/yr
|
- | |
| 09 | 2.7135: Install occupancy sensors | $324 | $350 |
$324
5,292
kWh
|
- | - | |
| 10 | 2.4133: Use most efficient type of electric motors | $108 | $224 |
$100
1,630
kWh
|
$8
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $98,064 | $39,892 |
$11,756
185,706
kWh
|
$804
-
kW-mo/yr
|
$85,504 | ||
| TOTAL IMPLEMENTED | $9,562 | $17,042 |
$9,052
141,521
kWh
|
$510
-
kW-mo/yr
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Primary Product Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs