Assessment Year | 2004 |
---|---|
Principal Product | Printed Circuit Boards |
NAICS | 334418: Printed Circuit Assembly (Electronic Assembly) Manufacturing |
SIC | 3679: Electronic Components, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 100 |
Plant Area |
55,000
ft2
|
Annual Production | 11,000
pieces
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $48,037 | 704,764 |
kWh
|
$0.068 |
Electricity Demand | $7,802 | 2,509 |
kW-mo/yr
|
$3.11 |
Electricity Fees | $565 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $33,541 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $24,614 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 4.322: Eliminate old stock and modify inventory control | $11,500 | $80 | - | - | - | $11,500 | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $9,783 | $400 |
$8,113
123,224
kWh
|
$1,670
-
kW-mo/yr
|
- | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,953 | $23,750 |
$3,357
50,868
kWh
|
$596
-
kW-mo/yr
|
- | - | |
04 | 2.7444: Close holes and openings in building such as broken windows | $3,384 | $15,950 | - | - |
$3,384
-
MMBtu
|
- | |
05 | 2.7232: Replace existing hvac unit with high efficiency model | $1,779 | $197 |
$1,591
24,100
kWh
|
$188
-
kW-mo/yr
|
- | - | |
06 | 2.6212: Turn off equipment during breaks, reduce operating time | $1,590 | $230 |
$1,590
24,090
kWh
|
- | - | - | |
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,263 | $30 |
$1,073
16,255
kWh
|
$190
-
kW-mo/yr
|
- | - | |
08 | 2.7135: Install occupancy sensors | $289 | $450 |
$289
4,378
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $33,541 | $41,087 |
$16,013
242,915
kWh
|
$2,644
-
kW-mo/yr
|
$3,384
-
MMBtu
|
$11,500 | ||
TOTAL IMPLEMENTED | $24,614 | $1,157 |
$11,066
167,957
kWh
|
$2,048
-
kW-mo/yr
|
- | $11,500 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs