Assessment Year | 1996 |
---|---|
Principal Product | Hydraulic Control Valves and Self Lubricated |
NAICS |
n/a
|
SIC | 3491: Industrial Valves |
Sales Range | $10 M to 50M |
# of Employees | 213 |
Plant Area |
52,000
ft2
|
Annual Production | 0
units
|
Production Hrs. Annual | 5,250
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $227,440 | 3,242,087 |
kWh
|
$0.070 |
Electricity Demand | $121,173 | 15,816 |
kW-mo/yr
|
$7.66 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $61,349 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $35,742 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings |
---|---|---|---|---|---|---|---|
01 | 2.4221: Install compressor air intakes in coolest locations | $11,373 | $21,500 |
$9,173
131,008
kWh
|
$2,200
-
kW-mo/yr
|
- | |
02 | 2.4133: Use most efficient type of electric motors | $9,900 | $13,282 |
$6,712
97,304
kWh
|
$3,188
-
kW-mo/yr
|
- | |
03 | 2.2622: Replace existing chiller with high efficiency model | $23,208 | $7,500 |
$12,862
183,763
kWh
|
$10,796
-
kW-mo/yr
|
$(-450.0)
-
Tgal
|
|
04 | 2.7232: Replace existing hvac unit with high efficiency model | $6,409 | $9,450 |
$4,427
63,306
kWh
|
$1,982
-
kW-mo/yr
|
- | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,780 | $17,184 |
$6,180
88,511
kWh
|
$1,600
-
kW-mo/yr
|
- | |
06 | 2.7135: Install occupancy sensors | $2,399 | $2,100 |
$2,399
34,291
kWh
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $280 | $450 |
$245
3,517
kWh
|
$35
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $61,349 | $71,466 |
$41,998
601,700
kWh
|
$19,801
-
kW-mo/yr
|
$(-450.0)
-
Tgal
|
||
TOTAL IMPLEMENTED | $35,742 | $61,866 |
$26,737
383,646
kWh
|
$9,005
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs