Assessment Year | 1996 |
---|---|
Principal Product | Continuous Buisness Forms |
NAICS |
n/a
|
SIC | 2761: Manifold Business Forms |
Sales Range | $5 M to 10M |
# of Employees | 93 |
Plant Area |
30,000
ft2
|
Annual Production | 2,500
ton
|
Production Hrs. Annual | 6,120
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $134,431 | 1,778,136 |
kWh
|
$0.076 |
Electricity Demand | $8,181 | 4,194 |
kW-mo/yr
|
$1.95 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $41,484 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $24,567 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings |
---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $224 | - |
$213
2,931
kWh
|
$11
-
kW-mo/yr
|
- | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,169 | - |
$1,108
14,654
kWh
|
$61
-
kW-mo/yr
|
- | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,213 | $40 |
$2,106
27,843
kWh
|
$107
-
kW-mo/yr
|
- | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $11,756 | $300 |
$11,190
148,007
kWh
|
$566
-
kW-mo/yr
|
- | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $144 | $240 |
$139
1,758
kWh
|
$5
-
kW-mo/yr
|
- | |
06 | 2.7135: Install occupancy sensors | $2,076 | $975 |
$2,076
27,550
kWh
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $15,920 | $18,749 |
$15,321
202,521
kWh
|
$599
-
kW-mo/yr
|
- | |
08 | 2.7314: Reduce ventilation air | $2,059 | $980 |
$1,805
24,033
kWh
|
$254
-
kW-mo/yr
|
- | |
09 | 2.7241: Install outside air damper / economizer on hvac unit | $1,510 | - |
$1,510
19,930
kWh
|
- | - | |
10 | 2.7232: Replace existing hvac unit with high efficiency model | $2,212 | $4,000 |
$1,938
25,791
kWh
|
$274
-
kW-mo/yr
|
- | |
11 | 2.7261: Install timers and/or thermostats | $746 | $1,600 |
$746
9,965
kWh
|
- | - | |
12 | 3.5313: Increase amount of waste recovered for resale | $1,455 | - | - | - |
$1,455
-
lb
|
|
TOTAL RECOMMENDED | $41,484 | $26,884 |
$38,152
504,983
kWh
|
$1,877
-
kW-mo/yr
|
$1,455
-
lb
|
||
TOTAL IMPLEMENTED | $24,567 | $19,764 |
$22,334
295,429
kWh
|
$778
-
kW-mo/yr
|
$1,455
-
lb
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs