Assessment Year 1996
Principal Product Continuous Buisness Forms
NAICS
n/a
SIC 2761: Manifold Business Forms
Sales Range $5
M
to 10
M
# of Employees 93
Plant Area 30,000
ft2
Annual Production 2,500
ton
Production Hrs. Annual 6,120
hrs
Location (State) Arizona

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $134,431 1,778,136
kWh
Electricity Demand $8,181 4,194
kW-mo/yr
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $41,484 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $24,567

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Solid Waste (non-haz) Savings
01 2.4231: Reduce the pressure of compressed air to the minimum required $224 - $213
2,931
kWh
$11
-
kW-mo/yr
-
02 2.4231: Reduce the pressure of compressed air to the minimum required $1,169 - $1,108
14,654
kWh
$61
-
kW-mo/yr
-
03 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $2,213 $40 $2,106
27,843
kWh
$107
-
kW-mo/yr
-
04 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $11,756 $300 $11,190
148,007
kWh
$566
-
kW-mo/yr
-
05 2.7142: Utilize higher efficiency lamps and/or ballasts $144 $240 $139
1,758
kWh
$5
-
kW-mo/yr
-
06 2.7135: Install occupancy sensors $2,076 $975 $2,076
27,550
kWh
- -
07 2.7142: Utilize higher efficiency lamps and/or ballasts $15,920 $18,749 $15,321
202,521
kWh
$599
-
kW-mo/yr
-
08 2.7314: Reduce ventilation air $2,059 $980 $1,805
24,033
kWh
$254
-
kW-mo/yr
-
09 2.7241: Install outside air damper / economizer on hvac unit $1,510 - $1,510
19,930
kWh
- -
10 2.7232: Replace existing hvac unit with high efficiency model $2,212 $4,000 $1,938
25,791
kWh
$274
-
kW-mo/yr
-
11 2.7261: Install timers and/or thermostats $746 $1,600 $746
9,965
kWh
- -
12 3.5313: Increase amount of waste recovered for resale $1,455 - - - $1,455
-
lb
TOTAL RECOMMENDED $41,484 $26,884 $38,152
504,983
kWh
$1,877
-
kW-mo/yr
$1,455
-
lb
TOTAL IMPLEMENTED $24,567 $19,764 $22,334
295,429
kWh
$778
-
kW-mo/yr
$1,455
-
lb
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Solid Waste (non-haz) Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs