Assessment Year 1996
Principal Product Garden and Lawn Components
NAICS
n/a
SIC 3052: Rubber and Plastics Hose and Belting
Sales Range $10
M
to 50
M
# of Employees 240
Plant Area 120,000
ft2
Annual Production 900
thousand feet
Production Hrs. Annual 8,136
hrs
Location (State) Arizona

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $146,527 2,380,422
kWh
Electricity Demand $15,608 5,338
kW-mo/yr
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $34,879 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Water Disposal Savings
01 2.7132: Install timers on light switches in little used areas $6,963 $450 n/a $6,023
97,890
kWh
$940
-
kW-mo/yr
-
02 2.7142: Utilize higher efficiency lamps and/or ballasts $5,024 $8,681 n/a $4,618
75,029
kWh
$406
-
kW-mo/yr
-
03 2.7135: Install occupancy sensors $1,509 $750 n/a $1,509
24,619
kWh
- -
04 2.7142: Utilize higher efficiency lamps and/or ballasts $258 $510 n/a $242
3,810
kWh
$16
-
kW-mo/yr
-
05 2.4231: Reduce the pressure of compressed air to the minimum required $2,187 - n/a $2,044
33,118
kWh
$143
-
kW-mo/yr
-
06 2.4133: Use most efficient type of electric motors $8,089 $5,005 n/a $7,528
122,216
kWh
$561
-
kW-mo/yr
-
07 2.4111: Utilize energy-efficient belts and other improved mechanisms $4,936 - n/a $4,597
74,736
kWh
$339
-
kW-mo/yr
-
08 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $1,190 $1,750 n/a $1,112
18,171
kWh
$78
-
kW-mo/yr
-
09 2.7232: Replace existing hvac unit with high efficiency model $2,295 $4,550 n/a $1,823
29,601
kWh
$472
-
kW-mo/yr
-
10 2.7261: Install timers and/or thermostats $606 $2,080 n/a $606
9,965
kWh
- -
11 3.4151: Minimize water usage $1,822 $3,000 n/a - - $1,822
-
Tgal
TOTAL RECOMMENDED $34,879 $26,776 $30,102
489,155
kWh
$2,955
-
kW-mo/yr
$1,822
-
Tgal
TOTAL IMPLEMENTED - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Water Disposal Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs