Assessment Year | 1994 |
---|---|
Principal Product | Color Advertisments |
NAICS |
n/a
|
SIC | 2752: Commercial Printing, Lithographic |
Sales Range | $10 M to 50M |
# of Employees | 245 |
Plant Area |
165,000
ft2
|
Annual Production | 427,856,720
pieces
|
Production Hrs. Annual | 7,904
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $972,805 | 13,260,258 |
kWh
|
$0.073 |
Natural Gas | $148,082 | 33,682 |
MMBtu
|
$4.40 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $445,255 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $29,087 | $49,812 |
$29,087
396,542
kWh
|
- | |
02 | 2.7111: Reduce illumination to minimum necessary levels | $1,051 | $320 |
$1,051
14,361
kWh
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,591 | $158 |
$1,591
21,688
kWh
|
- | |
04 | 2.7135: Install occupancy sensors | $1,081 | $975 |
$1,081
14,654
kWh
|
- | |
05 | 2.7134: Use photocell controls | $785 | $480 |
$785
10,844
kWh
|
- | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $168 | $200 |
$168
2,345
kWh
|
- | |
07 | 2.4133: Use most efficient type of electric motors | $18,178 | $10,473 |
$18,178
247,948
kWh
|
- | |
08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,525 | - |
$1,525
20,809
kWh
|
- | |
09 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,598 | $500 |
$1,598
21,688
kWh
|
- | |
10 | 2.2622: Replace existing chiller with high efficiency model | $54,627 | $156,250 |
$54,627
744,725
kWh
|
- | |
11 | 2.7444: Close holes and openings in building such as broken windows | $5,947 | $2,800 |
$5,947
81,184
kWh
|
- | |
12 | 2.2695: Use cascade system of recirculating during cold weather to avoid sub-cooling | $10,690 | $20,000 |
$10,690
145,662
kWh
|
- | |
13 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,746 | $4,972 |
$1,746
23,740
kWh
|
- | |
14 | 2.2511: Insulate bare equipment | $11,350 | $40,000 |
$11,350
154,748
kWh
|
- | |
15 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $305,831 | $1,059,725 |
$678,049
13,079,133
kWh
|
$(-372,218.0)
-
MMBtu
|
|
TOTAL RECOMMENDED | $445,255 | $1,346,665 |
$817,473
14,980,071
kWh
|
$(-372,218.0)
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs