| Assessment Year | 1994 |
|---|---|
| Principal Product | Gas Turbine Engines |
| NAICS |
n/a
|
| SIC | 3511: Steam, Gas, and Hydraulic Turbines, and Turbine Generator Set Units |
| Sales Range | $10 M to 50M |
| # of Employees | 123 |
| Plant Area |
160,000
ft2
|
| Annual Production | 1,200
pieces
|
| Production Hrs. Annual | 2,730
hrs
|
| Location (State) | Arizona |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $185,577 | 1,804,807 |
kWh
|
$0.10 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $48,039 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
|---|---|---|---|---|---|
| 01 | 2.4221: Install compressor air intakes in coolest locations | $434 | $300 |
$434
4,103
kWh
|
|
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $606 | $200 |
$606
5,862
kWh
|
|
| 03 | 2.2511: Insulate bare equipment | $1,549 | $588 |
$1,549
14,947
kWh
|
|
| 04 | 2.7234: Use heat pump for space conditioning | $17,728 | $34,200 |
$17,728
172,333
kWh
|
|
| 05 | 2.4133: Use most efficient type of electric motors | $1,100 | $2,367 |
$1,100
10,844
kWh
|
|
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,597 | $22,202 |
$12,597
122,509
kWh
|
|
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,955 | $16,200 |
$10,955
106,389
kWh
|
|
| 08 | 2.7135: Install occupancy sensors | $2,525 | $3,075 |
$2,525
24,619
kWh
|
|
| 09 | 2.7134: Use photocell controls | $545 | $60 |
$545
5,275
kWh
|
|
| TOTAL RECOMMENDED | $48,039 | $79,192 |
$48,039
466,881
kWh
|
||
| TOTAL IMPLEMENTED | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs