Assessment Year | 1994 |
---|---|
Principal Product | Aerospace Components |
NAICS |
n/a
|
SIC | 3499: Fabricated Metal Products, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 90 |
Plant Area |
25,000
ft2
|
Annual Production | 500,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $117,986 | 1,164,127 |
kWh
|
$0.10 |
Natural Gas | $637 | 44 |
MMBtu
|
$14.48 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $27,292 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $23,957 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,764 | $5,283 |
$8,764
86,460
kWh
|
|
02 | 2.7232: Replace existing hvac unit with high efficiency model | $4,565 | $12,000 |
$4,565
45,135
kWh
|
|
03 | 2.7444: Close holes and openings in building such as broken windows | $202 | - |
$202
2,052
kWh
|
|
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $8,758 | $1,000 |
$8,758
86,460
kWh
|
|
05 | 2.4314: Use synthetic lubricant | $3,017 | $1,098 |
$3,017
29,894
kWh
|
|
06 | 2.4133: Use most efficient type of electric motors | $1,256 | $975 |
$1,256
12,309
kWh
|
|
07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $614 | - |
$614
6,155
kWh
|
|
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $116 | $100 |
$116
1,172
kWh
|
|
TOTAL RECOMMENDED | $27,292 | $20,456 |
$27,292
269,637
kWh
|
||
TOTAL IMPLEMENTED | $23,957 | $19,258 |
$23,957
236,519
kWh
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs