Assessment Year | 1991 |
---|---|
Principal Product | CORRUGATED CONTAINERS |
NAICS |
n/a
|
SIC | 2653: Corrugated and Solid Fiber Boxes |
Sales Range | $10 M to 50M |
# of Employees | 150 |
Plant Area |
n/a
|
Annual Production | 720,000
thousand feet
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $262,553 | 4,008,499 |
kWh
|
$0.065 |
Natural Gas | $258,748 | 59,936 |
MMBtu
|
$4.32 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $219,100 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $175,405 | - |
$265,373
4,057,151
kWh
|
$(-89,968.0)
-
MMBtu
|
|
02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $12,714 | $1,000 | - |
$12,714
-
MMBtu
|
|
03 | 2.1221: Replace obsolete burners with more efficient ones | $4,459 | $100,000 | - |
$4,459
-
MMBtu
|
|
04 | 2.1131: Repair faulty insulation in furnaces, boilers, etc | $648 | $796 | - |
$648
-
MMBtu
|
|
05 | 2.2511: Insulate bare equipment | $9,504 | $1,290 | - |
$9,504
-
MMBtu
|
|
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,368 | $356 |
$5,368
82,063
kWh
|
- | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $831 | $935 |
$831
12,603
kWh
|
- | |
08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,428 | $300 |
$4,428
67,702
kWh
|
- | |
09 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,445 | - |
$2,445
37,515
kWh
|
- | |
10 | 2.6231: Utilize controls to operate equipment only when needed | $2,496 | $190 |
$2,496
38,101
kWh
|
- | |
11 | 2.4133: Use most efficient type of electric motors | $343 | $595 |
$343
5,275
kWh
|
- | |
12 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $459 | - |
$459
7,034
kWh
|
- | |
TOTAL RECOMMENDED | $219,100 | $105,462 |
$281,743
4,307,444
kWh
|
$(-62,643.0)
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs