Assessment Year | 1991 |
---|---|
Principal Product | ELECTROLYTIC FOIL |
NAICS |
n/a
|
SIC | 3679: Electronic Components, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 150 |
Plant Area |
n/a
|
Annual Production | 13,000,000
lb
|
Production Hrs. Annual | 8,250
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $4,197,633 | 82,888,630 |
kWh
|
$0.051 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $483,504 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.3416: Use combined cycle gas turbine generator sets with waste heat boilers connected to turbine exhaust | $420,880 | - |
$762,816
15,066,823
kWh
|
$(-341,936.0)
-
MMBtu
|
|
02 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $3,702 | $2,000 |
$5,173
102,286
kWh
|
$(-1,471.0)
-
MMBtu
|
|
03 | 2.2628: Utilize a less expensive cooling method | $9,652 | $36,000 |
$9,652
281,653
kWh
|
- | |
04 | 2.2443: Re-use or recycle hot or cold process exhaust air | $14,804 | $18,000 |
$14,804
292,497
kWh
|
- | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $6,073 | $12,775 |
$6,073
119,871
kWh
|
- | |
06 | 2.4133: Use most efficient type of electric motors | $1,852 | $2,168 |
$1,852
36,635
kWh
|
- | |
07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,293 | - |
$2,293
45,428
kWh
|
- | |
08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,724 | $500 |
$6,724
132,767
kWh
|
- | |
09 | 2.4221: Install compressor air intakes in coolest locations | $1,160 | $1,000 |
$1,160
22,860
kWh
|
- | |
10 | 2.7111: Reduce illumination to minimum necessary levels | $16,171 | - |
$16,171
319,461
kWh
|
- | |
11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $193 | - |
$193
3,810
kWh
|
- | |
TOTAL RECOMMENDED | $483,504 | $72,443 |
$826,911
16,424,091
kWh
|
$(-343,407.0)
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs