| Assessment Year | 1997 |
|---|---|
| Principal Product | Peanut Butter |
| NAICS |
n/a
|
| SIC | 2099: Food Preparations, Not Elsewhere Classified |
| Sales Range | $100 M to 500M |
| # of Employees | 110 |
| Plant Area |
143,000
ft2
|
| Annual Production | 127,000,000
lb
|
| Production Hrs. Annual | 6,497
hrs
|
| Location (State) | Arkansas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $354,995 | 16,415,006 |
kWh
|
$0.022 |
| Electricity Demand | $592,302 | 33,750 |
kW-mo/yr
|
$17.55 |
| Natural Gas | $114,906 | 32,612 |
MMBtu
|
$3.52 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $101,192 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $30,438 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7111: Reduce illumination to minimum necessary levels | $20,039 | $1,110 |
$20,039
360,492
kWh
|
- | - | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,439 | $3,524 |
$2,439
7,913
kWh
|
- | - | |
| 03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,961 | - |
$2,961
59,789
kWh
|
- | - | |
| 04 | 2.4221: Install compressor air intakes in coolest locations | $1,406 | $500 |
$1,406
36,635
kWh
|
- | - | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $907 | $90 |
$907
23,740
kWh
|
- | - | |
| 06 | 2.3136: Overlap custodial services with normal day hours | $498 | - |
$498
22,567
kWh
|
- | - | |
| 07 | 3.5311: Recover and reuse waste material | $48,811 | $10,230 | - |
$48,811
-
lb
|
- | |
| 08 | 3.5311: Recover and reuse waste material | $20,099 | $16,000 | - |
$20,099
-
lb
|
- | |
| 09 | 4.652: Replace existing equipment with more suitable substitutes | $4,032 | $21,600 | - | - | $4,032 | |
| TOTAL RECOMMENDED | $101,192 | $53,054 |
$28,250
511,136
kWh
|
$68,910
-
lb
|
$4,032 | ||
| TOTAL IMPLEMENTED | $30,438 | $41,214 |
$6,307
91,442
kWh
|
$20,099
-
lb
|
$4,032 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs