Assessment Year | 1997 |
---|---|
Principal Product | Air Filtration Media |
NAICS |
n/a
|
SIC | 3564: Industrial and Commercial Fans and Blowers and Air Purification Equipment |
Sales Range | $10 M to 50M |
# of Employees | 250 |
Plant Area |
88,957
ft2
|
Annual Production | 88,000,000
thousand feet
|
Production Hrs. Annual | 7,200
hrs
|
Location (State) | Arkansas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $219,934 | 6,675,850 |
kWh
|
$0.033 |
Electricity Demand | $65,760 | 11,624 |
kW-mo/yr
|
$5.66 |
Natural Gas | $282,814 | 106,872 |
MMBtu
|
$2.65 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $84,781 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $10,508 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Solid Waste (non-haz) Savings | Primary Product Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7111: Reduce illumination to minimum necessary levels | $2,654 | $690 |
$2,042
61,841
kWh
|
$612
-
kW-mo/yr
|
- | - | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,804 | $1,415 |
$2,128
64,478
kWh
|
$676
-
kW-mo/yr
|
- | - | - | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $856 | - |
$583
17,585
kWh
|
$273
-
kW-mo/yr
|
- | - | - | |
04 | 2.4221: Install compressor air intakes in coolest locations | $2,478 | $600 |
$1,927
58,324
kWh
|
$551
-
kW-mo/yr
|
- | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,578 | $350 |
$2,783
83,822
kWh
|
$795
-
kW-mo/yr
|
- | - | - | |
06 | 2.4133: Use most efficient type of electric motors | $10,942 | $17,710 |
$8,131
246,190
kWh
|
$2,811
-
kW-mo/yr
|
- | - | - | |
07 | 3.5315: Lease / purchase baler; sell cardboard to recycler | $853 | - | - | - | - |
$853
-
lb
|
- | |
08 | 3.4151: Minimize water usage | $616 | $100 | - | - |
$616
-
Tgal
|
- | - | |
09 | 4.651: Install back-up equipment | $60,000 | $54,000 | - | - | - | - | $60,000 | |
TOTAL RECOMMENDED | $84,781 | $74,865 |
$17,594
532,240
kWh
|
$5,718
-
kW-mo/yr
|
$616
-
Tgal
|
$853
-
lb
|
$60,000 | ||
TOTAL IMPLEMENTED | $10,508 | $2,555 |
$7,536
227,726
kWh
|
$2,356
-
kW-mo/yr
|
$616
-
Tgal
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Solid Waste (non-haz) Savings | Primary Product Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs