Assessment Year | 1996 |
---|---|
Principal Product | Water Faucets |
NAICS |
n/a
|
SIC | 3088: Plastics Plumbing Fixtures |
Sales Range | $500 k to 1M |
# of Employees | 175 |
Plant Area |
40,000
ft2
|
Annual Production | 1,040,000
pieces
|
Production Hrs. Annual | 7,508
hrs
|
Location (State) | Arkansas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $90,609 | 1,054,513 |
kWh
|
$0.086 |
Electricity Demand | $13,767 | 3,304 |
kW-mo/yr
|
$4.17 |
Natural Gas | $4,094 | 651 |
MMBtu
|
$6.29 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $20,976 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $11,876 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (haz) Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.2511: Insulate bare equipment | $1,071 | $140 |
$982
13,482
kWh
|
$89
-
kW-mo/yr
|
- | - | |
02 | 2.4221: Install compressor air intakes in coolest locations | $203 | $50 |
$186
2,638
kWh
|
$17
-
kW-mo/yr
|
- | - | |
03 | 2.7111: Reduce illumination to minimum necessary levels | $3,535 | $751 |
$3,211
43,962
kWh
|
$324
-
kW-mo/yr
|
- | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,272 | $235 |
$1,166
16,120
kWh
|
$106
-
kW-mo/yr
|
- | - | |
05 | 2.4133: Use most efficient type of electric motors | $1,858 | $1,460 |
$1,676
22,860
kWh
|
$182
-
kW-mo/yr
|
- | - | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $577 | - |
$515
7,034
kWh
|
$62
-
kW-mo/yr
|
- | - | |
07 | 3.7311: Maintain machines to reduce leaks | $3,360 | $600 | - | - |
$3,360
-
gal
|
- | |
08 | 2.8211: Consolidate freight shipments and/or deliveries | $9,100 | - | - | - | - | $9,100 | |
TOTAL RECOMMENDED | $20,976 | $3,236 |
$7,736
106,096
kWh
|
$780
-
kW-mo/yr
|
$3,360
-
gal
|
$9,100 | ||
TOTAL IMPLEMENTED | $11,876 | $3,236 |
$7,736
106,096
kWh
|
$780
-
kW-mo/yr
|
$3,360
-
gal
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (haz) Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs