| Assessment Year | 1996 |
|---|---|
| Principal Product | 12,000 Btu Fuel |
| NAICS |
n/a
|
| SIC | 2869: Industrial Organic Chemicals, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 225 |
| Plant Area |
54,000
ft2
|
| Annual Production | 9,900,000
Tgal
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Arkansas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $43,095 | 2,076,788 |
kWh
|
$0.021 |
| Electricity Demand | $79,832 | 4,469 |
kW-mo/yr
|
$17.86 |
| Natural Gas | $730 | 129 |
MMBtu
|
$5.66 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $78,911 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $78,911 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4133: Use most efficient type of electric motors | $4,133 | $7,570 |
$1,418
67,409
kWh
|
$2,715
-
kW-mo/yr
|
- | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,604 | $364 |
$738
35,170
kWh
|
$866
-
kW-mo/yr
|
- | |
| 03 | 2.7111: Reduce illumination to minimum necessary levels | $6,114 | $80 |
$1,279
61,254
kWh
|
$4,835
-
kW-mo/yr
|
- | |
| 04 | 2.4221: Install compressor air intakes in coolest locations | $337 | $100 |
$290
13,775
kWh
|
$47
-
kW-mo/yr
|
- | |
| 05 | 2.1114: Limit and control secondary combustion air in furnace | $41,971 | $11,500 |
$19,316
919,402
kWh
|
$22,655
-
kW-mo/yr
|
- | |
| 06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $608 | - |
$153
7,327
kWh
|
$455
-
kW-mo/yr
|
- | |
| 07 | 3.5315: Lease / purchase baler; sell cardboard to recycler | $24,144 | $1,000 | - | - |
$24,144
-
lb
|
|
| TOTAL RECOMMENDED | $78,911 | $20,614 |
$23,194
1,104,337
kWh
|
$31,573
-
kW-mo/yr
|
$24,144
-
lb
|
||
| TOTAL IMPLEMENTED | $78,911 | $20,614 |
$23,194
1,104,337
kWh
|
$31,573
-
kW-mo/yr
|
$24,144
-
lb
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs