Assessment Year | 1995 |
---|---|
Principal Product | Wrinkle-Free Shirts and Pants |
NAICS |
n/a
|
SIC | 2329: Men's and Boys' Clothing, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 200 |
Plant Area |
64,000
ft2
|
Annual Production | 3,120,000
pieces
|
Production Hrs. Annual | 6,257
hrs
|
Location (State) | Arkansas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $199,521 | 2,592,321 |
kWh
|
$0.077 |
Natural Gas | $82,928 | 21,895 |
MMBtu
|
$3.79 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $111,769 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $17,958 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Water Disposal Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7111: Reduce illumination to minimum necessary levels | $6,271 | $3,600 |
$6,271
84,408
kWh
|
- | - | - | |
02 | 2.3212: Optimize plant power factor | $2,641 | $4,320 |
$2,641
-
kWh
|
- | - | - | |
03 | 2.4221: Install compressor air intakes in coolest locations | $1,124 | $300 |
$1,124
15,240
kWh
|
- | - | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,644 | $150 |
$3,644
46,307
kWh
|
- | - | - | |
05 | 2.4133: Use most efficient type of electric motors | $6,229 | $5,120 |
$6,229
83,529
kWh
|
- | - | - | |
06 | 2.7241: Install outside air damper / economizer on hvac unit | $90,655 | $8,400 |
$90,655
1,353,458
kWh
|
- | - | - | |
07 | 2.1213: Direct warmest air to combustion intake | $515 | $600 | - |
$515
-
MMBtu
|
- | - | |
08 | 2.1233: Analyze flue gas for proper air/fuel ratio | $515 | $1,000 | - |
$515
-
MMBtu
|
- | - | |
09 | 3.4151: Minimize water usage | $175 | $200 | - | - |
$21
-
Tgal
|
$154
-
Tgal
|
|
TOTAL RECOMMENDED | $111,769 | $23,690 |
$110,564
1,582,942
kWh
|
$1,030
-
MMBtu
|
$21
-
Tgal
|
$154
-
Tgal
|
||
TOTAL IMPLEMENTED | $17,958 | $10,370 |
$17,268
229,484
kWh
|
$515
-
MMBtu
|
$21
-
Tgal
|
$154
-
Tgal
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Water Disposal Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs