Assessment Year | 1995 |
---|---|
Principal Product | Fabricated Structural Steel |
NAICS |
n/a
|
SIC | 3441: Fabricated Structural Metal |
Sales Range | $50 M to 100M |
# of Employees | 212 |
Plant Area |
650,000
ft2
|
Annual Production | 35,000
ton
|
Production Hrs. Annual | 4,589
hrs
|
Location (State) | Arkansas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $339,678 | 4,501,172 |
kWh
|
$0.075 |
Natural Gas | $63,953 | 19,361 |
MMBtu
|
$3.30 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $74,921 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $74,921 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,497 | $489 |
$1,497
16,413
kWh
|
- | |
02 | 2.7111: Reduce illumination to minimum necessary levels | $28,580 | $10,560 |
$28,580
357,855
kWh
|
- | |
03 | 2.4221: Install compressor air intakes in coolest locations | $2,030 | $100 |
$2,030
28,136
kWh
|
- | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $17,221 | $500 |
$17,221
238,863
kWh
|
- | |
05 | 2.4133: Use most efficient type of electric motors | $7,947 | $13,110 |
$7,947
107,562
kWh
|
- | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,719 | - |
$2,719
38,687
kWh
|
- | |
07 | 2.7231: Use radiant heater for spot heating | $14,927 | $18,400 | - |
$14,927
-
MMBtu
|
|
TOTAL RECOMMENDED | $74,921 | $43,159 |
$59,994
787,516
kWh
|
$14,927
-
MMBtu
|
||
TOTAL IMPLEMENTED | $74,921 | $43,159 |
$59,994
787,516
kWh
|
$14,927
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs