Assessment Year | 1994 |
---|---|
Principal Product | Corrugated Paper-board Boxes |
NAICS |
n/a
|
SIC | 2653: Corrugated and Solid Fiber Boxes |
Sales Range | $10 M to 50M |
# of Employees | 150 |
Plant Area |
200,000
ft2
|
Annual Production | 660,000
thousand feet
|
Production Hrs. Annual | 6,570
hrs
|
Location (State) | Arkansas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $326,777 | 4,949,004 |
kWh
|
$0.066 |
Natural Gas | $154,733 | 52,068 |
MMBtu
|
$2.97 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $54,534 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $28,139 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,196 | $250 |
$4,196
63,599
kWh
|
- | - | |
02 | 2.2135: Repair and eliminate steam leaks | $7,934 | $1,000 | - |
$7,934
-
MMBtu
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,963 | $597 |
$1,963
29,601
kWh
|
- | - | |
04 | 2.7111: Reduce illumination to minimum necessary levels | $5,155 | $270 |
$5,155
77,960
kWh
|
- | - | |
05 | 2.4133: Use most efficient type of electric motors | $1,397 | $2,720 |
$1,397
21,102
kWh
|
- | - | |
06 | 2.4221: Install compressor air intakes in coolest locations | $991 | $100 |
$991
14,947
kWh
|
- | - | |
07 | 2.1233: Analyze flue gas for proper air/fuel ratio | $6,503 | $1,000 | - |
$6,503
-
MMBtu
|
- | |
08 | 2.4134: Replace electric motor with fossil fuel engine | $24,683 | $24,000 |
$37,512
568,288
kWh
|
$(-8,829.0)
-
MMBtu
|
$(-4,000.0) | |
09 | 2.2511: Insulate bare equipment | $1,712 | $1,204 | - |
$1,712
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $54,534 | $31,141 |
$51,214
775,497
kWh
|
$7,320
-
MMBtu
|
$(-4,000.0) | ||
TOTAL IMPLEMENTED | $28,139 | $5,937 |
$13,702
207,209
kWh
|
$14,437
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs